Diagnosis
Messages – faults and alarms
6-218
E Siemens AG, 2004. All rights reserved
SINAMICS S120 Installation and Start-Up Manual, 12/04 Edition
Acknowledging faults
The list of faults and alarms specifies how each fault is acknowledged after the
cause has been remedied.
1. Acknowledgement of faults by “POWER ON”
Switch the drive on/off (POWER ON)
Press the RESET button on the Control Unit
2. Acknowledgement of faults by “IMMEDIATE”
Via PROFIBUS control signal
STW1.7 (reset fault memory): 0/1edge
Set STW1.0 (ON/OFF1) = “0” and “1”
Via external input signal
Binector input and interconnection with digital input
p2103[0...n] = “desired signal source”
p2104[0...n] = “desired signal source”
p2105[0...n] = “desired signal source”
Note
The drive cannot resume operation until all active faults have been acknowledged.