Basic Information about the Drive System
Parameters
7-228
E Siemens AG, 2004. All rights reserved
SINAMICS S120 Installation and Start-Up Manual, 12/04 Edition
Saving parameters in a non-volatile memory
The modified parameter values are stored in the volatile RAM. When the drive sys-
tem is switched off, this data is lost.
The data has to be saved as follows in a non-volatile memory so that it is available
the next time the drive is switched on.
S Save parameters – device and all drives
p0977 = 1 Is automatically reset to 0
S Save parameters with STARTER
See “Copy from RAM to ROM” function
Resetting parameters
The parameters can be reset to the factory setting as follows:
S Resetting parameters – All parameters for “Control Unit” drive object
p0009 = 30 Parameter reset
p0976 = 1 Is automatically reset to 0