EasyManua.ls Logo

Siemens SINAMICS S120 - Page 244

Siemens SINAMICS S120
294 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Basic Information about the Drive System
BICO technology: interconnection of signals
7-244
E Siemens AG, 2004. All rights reserved
SINAMICS S120 Installation and Start-Up Manual, 12/04 Edition
Scaling for object A_Inf
Table 7-7 Scaling for object A_Inf
Size
Scaling parameters Default at first commissioning
Reference frequency 100 % = p2000 p2000 = p0211
Reference voltage 100 % = p2001 p2001 = r0206/r0207
Reference current 100 % = p2002 p2002 = p0207
Reference power 100 % = r2004 r2004 = p0206
Reference control factor 100 % = Maximum output voltage
without overload
-
Reference temperature 100 % = 100°C -
Reference electrical angle 100 % = 90° -
Scaling for object B_Inf
Table 7-8 Scaling for object B_Inf
Size
Scaling parameters Default at first commissioning
Reference frequency 100 % = p2000 p2000 = 50
Reference voltage 100 % = p2001 p2001 = r0206/r0207
Reference current 100 % = p2002 p2002 = p0207
Reference power 100 % = r2004 r2004 = p0206
Reference temperature 100 % = 100°C -
Reference electrical angle 100 % = 90° -