Preparations for Commissioning
Rules for wiring with DRIVE-CLiQ
2-36
E Siemens AG, 2004. All rights reserved
SINAMICS S120 Installation and Start-Up Manual, 12/04 Edition
Rules for FW2.2:
S Only one Active Line Module can be connected to a Control Unit.
S The default sampling times must not be changed.
S A Double Motor Module must not be operated as a single drive.
S Mixed operation (servo with vector V/f) is possible.
S A maximum of nine Sensor Modules can be connected.
S The Active Line Module (booksize) and Motor Modules (booksize)
– can be connected to one DRIVE-CLiQ line in servo mode.
– must be connected to separate DRIVE-CLiQ lines in vector mode.
S During mixed operation (servo and vector V/f), separate DRIVE-CLiQ lines
must be used.
S The Active Line Module (chassis) and the Motor Modules (chassis) must be
connected to separate DRIVE-CLiQ lines.
S Motor Modules (chassis) with different pulse frequencies must be connected to
separate DRIVE-CLiQ lines.
Table 2-7 Maximum number of drives that can be controlled by a Control Unit 320
Servo Vector V/f (=vector without
speed control function
module)
Vector
Number of
components
1 Active Line Module +
6 Motor Modules
1 Active Line Module +
4 Motor Modules
(sampling time of current
controller: 250 µs)
1 Active Line Module +
6 Motor Modules
(sampling time of current
controller: 400 µs)
1 Active Line Module +
2 Motor Modules
(sampling time of current
controller:
250 µs / speed controller:
1000 µs)
1 Active Line Module +
4 Motor Modules
(sampling time of current
Servo and vector V/f:
1 Active Line Module + 5 Motor Modules
(servo: current controller: 125 µs / speed controller:
125 µs
Vector V/f:
Sampling time of current controller: 250 µs with max. 2 V/f
drives
Sampling time of current controller: 400 µs with more than
2 V/f drives)
(sampling time of current
controller:
400 µs / speed controller:
1600 µs)
Note:
In addition, the “Safe standstill” function can be activated and a TM31 connected.
No function modules must be activated.