Circuit breaker is open. The feeder is isolated (zero voltage). The VTmcb's of both voltage transformer
circuits must be closed.
For the synchronism check the program AR OVERRIDE = YES (address 3519) is set; the other programs
(addresses 3515 to 3518) are set to NO.
Via binary input (No.2906
>Sync. Start AR
) initiate the measuring request. The synchronism check
must release closing (message
Sync. release
, No. 2951). If not, check all relevant parameters again
(synchrocheck configured and enabled correctly, see Sections 2.1.1.2 Setting Notes, 2.1.3.1 Setting
Notes and 2.4.2 Setting Notes).
Address 3519 AR OVERRIDE must be set to NO.
Then the circuit breaker is closed while the line isolator is open (see Figure 3-25). Both voltage trans-
formers therefore measure the same voltage.
The programAR SYNC-CHECK = YES (address 3515) is set for synchronism check.
Via binary input (No.2906
>Sync. Start AR
) initiate the measuring request. The synchronism check
must release closing (message
Sync. release
, No.2951).
[synchronkontrolle-messspannungen-250702-kn, 1, en_GB]
Figure 3-25 Measuring voltages for the synchrocheck — example
If not, first check whether one of the before named messages 2947
Sync. Udiff>
or 2949
Sync. φ-
diff>
is available in the spontaneous messages.
The indication
Sync. Udiff>
indicates that the magnitude (ratio) adaptation is incorrect. Check
address 215 Usy1/Usy2 ratio and recalculate the adaptation factor, if necessary.
The indication
Sync. φ-diff>
indicates that the phase relation, in this example of the busbar voltage,
does not match the setting at address 212 Usy2 connection (see Section 2.1.3.1 Setting Notes).
When measuring across a transformer, address 214 φ Usy2-Usy1 must also be checked; this must
adapt the vector group (see Section2.1.3.1 Setting Notes). If these are correct, there is probably a reverse
polarity of the voltage transformer terminals forU
sy2
.
The program AR Usy1>Usy2< = YES (address 3517) and AR SYNC-CHECK = YES (address 3515) is set
for synchronism check.
Open the VT mcb of the measuring point U
sy2
(No. 362
>FAIL:U4 VT
).
Via binary input (No.2906
>Sync. Start AR
) a measuring request is entered. There is no close release.
If there is, the VT mcb for the measuring point U
sy2
is not allocated. Check whether this is the required
state, alternatively check the binary input
>FAIL:U4 VT
(No. 362).
Reclose the VT mcb of the measuring point U
sy2
.
Open the circuit breaker.
The program AR Usy1<Usy2> = YES (address 3516) and AR Usy1>Usy2< = NO (address 3517) is set
for synchronism check.
Mounting and Commissioning
3.3 Commissioning
218 SIPROTEC 4, 7VK61, Manual
C53000-G1176-C159-5, Edition 05.2018