Addr. Parameter Function C Setting Options Default Setting Comments
242 T-CBtest-dead P.System Data
1
0.00 .. 30.00 sec 0.10 sec Dead Time for CB test-
autoreclosure
302 CHANGE Change Group Group A
Group B
Group C
Group D
Binary Input
Protocol
Group A Change to Another
Setting Group
402A WAVEFORM-
TRIGGER
Osc. Fault Rec. Save w. Pickup
Save w. TRIP
Start w. TRIP
Save w. Pickup Waveform Capture
403A WAVEFORM DATA Osc. Fault Rec. Fault event
Pow.Sys.Flt.
Fault event Scope of Waveform Data
410 MAX. LENGTH Osc. Fault Rec. 0.30 .. 5.00 sec 2.00 sec Max. length of a Wave-
form Capture Record
411 PRE. TRIG. TIME Osc. Fault Rec. 0.05 .. 0.50 sec 0.25 sec Captured Waveform Prior
to Trigger
412 POST REC. TIME Osc. Fault Rec. 0.05 .. 0.50 sec 0.10 sec Captured Waveform after
Event
415 BinIn CAPT.TIME Osc. Fault Rec. 0.10 .. 5.00 sec 0.50 sec Capture Time via Binary
Input
610 FltDisp.LED/LCD Device Target on PU
Target on TRIP
Target on PU Fault Display on LED / LCD
625A T MIN LED HOLD Device 0 .. 60 min 0 min Minimum hold time of
latched LEDs
640 Start image DD Device image 1
image 2
image 3
image 4
image 5
image 6
image 1 Start image Default
Display
1103 FullScaleVolt. P.System Data
2
1.0 .. 1200.0 kV 400.0 kV Measurement: Full Scale
Voltage (100%)
1104 FullScaleCurr. P.System Data
2
10 .. 5000 A 1000 A Measurement: Full Scale
Current (100%)
1107 P,Q sign P.System Data
2
not reversed
reversed
not reversed P,Q operational measured
values sign
1130A PoleOpenCurrent P.System Data
2
1A 0.05 .. 1.00 A 0.10 A Pole Open Current
Threshold
5A 0.25 .. 5.00 A 0.50 A
1131A PoleOpenVoltage P.System Data
2
2 .. 70 V 30 V Pole Open Voltage
Threshold
1135 Reset Trip CMD P.System Data
2
CurrentOpenPole
Current AND CB
Pickup Reset
CurrentOpenPole RESET of Trip Command
1136 OpenPoleDetect. P.System Data
2
OFF
Current AND CB
w/ measurement
w/ measurement open pole detector
1150A SI Time Man.Cl P.System Data
2
0.01 .. 30.00 sec 0.30 sec Seal-in Time after
MANUAL closures
Functions, Settings, Information
E.2 Settings
288 SIPROTEC 4, 7VK61, Manual
C53000-G1176-C159-5, Edition 05.2018