Addr. Parameter Function C Setting Options Default Setting Comments
1151 MAN. CLOSE P.System Data
2
with Sync-check
w/o Sync-check
NO
NO Manual CLOSE
COMMAND generation
1152 Man.Clos. Imp. P.System Data
2
OBJVERWparaMEIN-
STELL
none MANUAL Closure Impulse
after CONTROL
2601 Operating Mode Back-Up O/C ON
OFF
ON Operating mode
2610 Iph>> Back-Up O/C 1A 0.05 .. 50.00 A 2.00 A Iph>> Pickup
5A 0.25 .. 250.00 A 10.00 A
2611 T Iph>> Back-Up O/C 0.00 .. 30.00 sec 0.30 sec T Iph>> Time delay
2612 3I0>> PICKUP Back-Up O/C 1A 0.05 .. 25.00 A 0.50 A 3I0>> Pickup
5A 0.25 .. 125.00 A 2.50 A
2613 T 3I0>> Back-Up O/C 0.00 .. 30.00 sec 2.00 sec T 3I0>> Time delay
2614 I>> InstTrip BI Back-Up O/C NO
YES
YES Instantaneous trip via BI
2615 I>> SOTF Back-Up O/C NO
YES
NO Instantaneous trip after
SwitchOnToFault
2620 Iph> Back-Up O/C 1A 0.05 .. 50.00 A 1.50 A Iph> Pickup
5A 0.25 .. 250.00 A 7.50 A
2621 T Iph> Back-Up O/C 0.00 .. 30.00 sec 0.50 sec T Iph> Time delay
2622 3I0> Back-Up O/C 1A 0.05 .. 25.00 A 0.20 A 3I0> Pickup
5A 0.25 .. 125.00 A 1.00 A
2623 T 3I0> Back-Up O/C 0.00 .. 30.00 sec 2.00 sec T 3I0> Time delay
2624 I> Telep/BI Back-Up O/C NO
YES
NO Instantaneous trip via
Teleprot./BI
2625 I> SOTF Back-Up O/C NO
YES
NO Instantaneous trip after
SwitchOnToFault
2630 Iph> STUB Back-Up O/C 1A 0.05 .. 50.00 A 1.50 A Iph> STUB Pickup
5A 0.25 .. 250.00 A 7.50 A
2631 T Iph STUB Back-Up O/C 0.00 .. 30.00 sec 0.30 sec T Iph STUB Time delay
2632 3I0> STUB Back-Up O/C 1A 0.05 .. 25.00 A 0.20 A 3I0> STUB Pickup
5A 0.25 .. 125.00 A 1.00 A
2633 T 3I0 STUB Back-Up O/C 0.00 .. 30.00 sec 2.00 sec T 3I0 STUB Time delay
2634 I-STUB Telep/BI Back-Up O/C NO
YES
NO Instantaneous trip via
Teleprot./BI
2635 I-STUB SOTF Back-Up O/C NO
YES
NO Instantaneous trip after
SwitchOnToFault
2640 Ip> Back-Up O/C 1A 0.10 .. 4.00 A 2147483647 A Ip> Pickup
5A 0.50 .. 20.00 A 2147483647 A
2642 T Ip Time Dial Back-Up O/C 0.05 .. 3.00 sec 0.50 sec T Ip Time Dial
2643 Time Dial TD Ip Back-Up O/C 0.50 .. 15.00 5.00 Time Dial TD Ip
2646 T Ip Add Back-Up O/C 0.00 .. 30.00 sec 0.00 sec T Ip Additional Time Delay
2650 3I0p PICKUP Back-Up O/C 1A 0.05 .. 4.00 A 2147483647 A 3I0p Pickup
5A 0.25 .. 20.00 A 2147483647 A
2652 T 3I0p TimeDial Back-Up O/C 0.05 .. 3.00 sec 0.50 sec T 3I0p Time Dial
2653 TimeDial TD3I0p Back-Up O/C 0.50 .. 15.00 5.00 Time Dial TD 3I0p
2656 T 3I0p Add Back-Up O/C 0.00 .. 30.00 sec 0.00 sec T 3I0p Additional Time
Delay
Functions, Settings, Information
E.2 Settings
SIPROTEC 4, 7VK61, Manual 289
C53000-G1176-C159-5, Edition 05.2018