No. Description Function Typ
e of
Info
rma
tion
Log Buffers Configurable in Matrix IEC 60870-5-103
Event Log ON/OFF
Trip (Fault) Log ON/OFF
Ground Fault Log ON/OFF
Marked in Oscill. Record
LED
Binary Input
Function Key
Relay
Chatter Suppression
Type
information number
Data Unit
General Interrogation
7221 Backup O/C TRIP I>> (O/C
TRIP I>>)
Back-Up O/C OUT * ON * LED BO 64 12
1
2 No
7222 Backup O/C TRIP I> (O/C
TRIP I>)
Back-Up O/C OUT * ON * LED BO 64 12
2
2 No
7223 Backup O/C TRIP Ip (O/C
TRIP Ip)
Back-Up O/C OUT * ON * LED BO 64 12
3
2 No
7235 O/C I-STUB TRIP (I-STUB
TRIP)
Back-Up O/C OUT * ON * LED BO 64 13
5
2 No
7325 CB1-TEST TRIP command -
Only L1 (CB1-TESTtrip L1)
Testing OUT O
N
OF
F
* * LED BO 15
3
25 1 Yes
7326 CB1-TEST TRIP command -
Only L2 (CB1-TESTtrip L2)
Testing OUT O
N
OF
F
* * LED BO 15
3
26 1 Yes
7327 CB1-TEST TRIP command -
Only L3 (CB1-TESTtrip L3)
Testing OUT O
N
OF
F
* * LED BO 15
3
27 1 Yes
7328 CB1-TEST TRIP command
L123 (CB1-TESTtrip123)
Testing OUT O
N
OF
F
* * LED BO 15
3
28 1 Yes
7329 CB1-TEST CLOSE
command (CB1-TEST
close)
Testing OUT O
N
OF
F
* * LED BO 15
3
29 1 Yes
7345 CB-TEST is in progress
(CB-TEST running)
Testing OUT O
N
OF
F
* * LED BO 15
3
45 1 Yes
7346 CB-TEST canceled due to
Power Sys. Fault (CB-
TSTstop FLT.)
Testing OUT
_Ev
O
N
*
7347 CB-TEST canceled due to
CB already OPEN (CB-
TSTstop OPEN)
Testing OUT
_Ev
O
N
*
7348 CB-TEST canceled due to
CB was NOT READY (CB-
TSTstop NOTr)
Testing OUT
_Ev
O
N
*
7349 CB-TEST canceled due to
CB stayed CLOSED (CB-
TSTstop CLOS)
Testing OUT
_Ev
O
N
*
Functions, Settings, Information
E.3 Information List
334 SIPROTEC 4, 7VK61, Manual
C53000-G1176-C159-5, Edition 05.2018