No. Description Function Typ
e of
Info
rma
tion
Log Buffers Configurable in Matrix IEC 60870-5-103
Event Log ON/OFF
Trip (Fault) Log ON/OFF
Ground Fault Log ON/OFF
Marked in Oscill. Record
LED
Binary Input
Function Key
Relay
Chatter Suppression
Type
information number
Data Unit
General Interrogation
7350 CB-TEST was successful
(CB-TST .OK.)
Testing OUT
_Ev
O
N
*
10201 >BLOCK Uph-e>(>) Over-
volt. (phase-earth) (>Uph-
e>(>) BLK)
Voltage
Prot.
SP * * * LED BI BO
10202 >BLOCK Uph-ph>(>)
Overvolt (phase-phase)
(>Uph-ph>(>) BLK)
Voltage
Prot.
SP * * * LED BI BO
10203 >BLOCK 3U0>(>) Over-
volt. (zero sequence)
(>3U0>(>) BLK)
Voltage
Prot.
SP * * * LED BI BO
10204 >BLOCK U1>(>) Overvolt.
(positive seq.) (>U1>(>)
BLK)
Voltage
Prot.
SP * * * LED BI BO
10205 >BLOCK U2>(>) Overvolt.
(negative seq.) (>U2>(>)
BLK)
Voltage
Prot.
SP * * * LED BI BO
10206 >BLOCK Uph-e<(<)
Undervolt (phase-earth)
(>Uph-e<(<) BLK)
Voltage
Prot.
SP * * * LED BI BO
10207 >BLOCK Uphph<(<)
Undervolt (phase-phase)
(>Uphph<(<) BLK)
Voltage
Prot.
SP * * * LED BI BO
10208 >BLOCK U1<(<) Undervolt
(positive seq.) (>U1<(<)
BLK)
Voltage
Prot.
SP * * * LED BI BO
10215 Uph-e>(>) Overvolt. is
switched OFF (Uph-e>(>)
OFF)
Voltage
Prot.
OUT O
N
OF
F
* * LED BO 73 15 1 Yes
10216 Uph-e>(>) Overvolt. is
BLOCKED (Uph-e>(>) BLK)
Voltage
Prot.
OUT O
N
OF
F
ON
OFF
* LED BO 73 16 1 Yes
10217 Uph-ph>(>) Overvolt. is
switched OFF (Uph-
ph>(>) OFF)
Voltage
Prot.
OUT O
N
OF
F
* * LED BO 73 17 1 Yes
10218 Uph-ph>(>) Overvolt. is
BLOCKED (Uph-ph>(>)
BLK)
Voltage
Prot.
OUT O
N
OF
F
ON
OFF
* LED BO 73 18 1 Yes
Functions, Settings, Information