EasyManua.ls Logo

Siemens siprotec 7SA522 - Page 131

Siemens siprotec 7SA522
628 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Configuration
5-337SA522 Manual
C53000-G1176-C119-2
The settings for the monitoring criteria of the chatter blocking feature are set only once
for all binary inputs; however, the status of the chatter suppression can be set individ-
ually for each binary input. See “Filtering / Contact Chatter Suppression” in Sub-sec-
tion 5.2.3.
The following should be noted:
If there is contact chatter at a binary input and the input is blocked, the correspond-
ing indication will be displayed with “CCF” (example: “!'RRURSHQ&&)21”). Al-
so, the indication “&RQWDFWFKDWWHUILOWHU” reports this condition. Both mes-
sages are shown in the operating buffer.
Chattering of a single point indication is set as ON (coming) if the binary input has
been in an active state.
Chattering of a single point indication is set as OFF (going) if the binary input has
been in an inactive state.
If this behaviour causes undesired results in individual situations, a blocking may
be configured in CFC.
Chattering of a double point indication will be considered an “intermediate” condi-
tion.
Note:
Chatter blocking cannot be activated for any of the standard protective indications.

Table of Contents

Other manuals for Siemens siprotec 7SA522

Related product manuals