EasyManua.ls Logo

Siemens siprotec 7SA522 - Applying the Function Parameter Settings

Siemens siprotec 7SA522
628 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Functions
6-717SA522 Manual
C53000-G1176-C119-2
6.2.5.2 Applying the Function Parameter Settings
The trip delay times of the distance stages and intervention options which are also
processed in the tripping logic of the distance protection were already considered with
the zone settings (Sub-sections 6.2.3.2 and 6.2.4.2).
The parameter in address  627)]RQH which determines the response during
switching onto a short-circuit was already set as part of the general data of the dis-
tance protection (Sub-section 6.2.2.2).
Further setting options which affect the tripping are described as part of the tripping
logic of the device (refer to Sub-section 6.17.4).

Table of Contents

Other manuals for Siemens siprotec 7SA522

Related product manuals