Addr. Setting Title Setting Options Default Setting Comments
3201 FCT Telep. E/F ON
OFF
ON Teleprotection for Earth Fault O/
C
3202 Line Config. Two Terminals
Three Terminals
Two Terminals Line Configuration
3203 Send Prolong. 0.00..30.00 sec 0.05 sec Time for send signal prolonga-
tion
3207 Delay for alarm 0.00..30.00 sec 10.00 sec Unblocking: Time Delay for
Alarm
3208 Release Delay 0.000..30.000 sec 0.000 sec Time Delay for release after pik-
kup
3209 TrBlk Wait Time 0.00..30.00 sec 0.04 sec Transient Block.: Duration exter-
nal flt.
3210 TrBlk BlockTime 0.00..30.00 sec 0.05 sec Transient Block.: Blk.T. after ext.
flt.
F.No. Alarm Comments
1311 >EF Teleprot.ON >E/F Teleprotection ON
1312 >EF TeleprotOFF >E/F Teleprotection OFF
1313 >EF TeleprotBLK >E/F Teleprotection BLOCK
1318 >EF Rec.Ch1 >E/F Carrier RECEPTION, Channel 1
1319 >EF Rec.Ch2 >E/F Carrier RECEPTION, Channel 2
1320 >EF UB ub 1 >E/F Unblocking: UNBLOCK, Channel 1
1321 >EF UB bl 1 >E/F Unblocking: BLOCK, Channel 1
1322 >EF UB ub 2 >E/F Unblocking: UNBLOCK, Channel 2
1323 >EF UB bl 2 >E/F Unblocking: BLOCK, Channel 2
1324 >EF BlkEcho >E/F BLOCK Echo Signal
1380 EF TeleON/offBI E/F Teleprot. ON/OFF via BI
1381 EF Telep. OFF E/F Teleprotection is switched OFF
1384 EF Tele SEND E/F Telep. Carrier SEND signal
1386 EF TeleTransBlk E/F Telep. Transient Blocking
1387 EF TeleUB Fail1 E/F Telep. Unblocking: FAILURE Channel 1
1388 EF TeleUB Fail2 E/F Telep. Unblocking: FAILURE Channel 2
1389 EF Tele BL STOP E/F Telep. Blocking: carrier STOP signal
1390 EF Tele BL Jump E/F Tele.Blocking: Send signal with jump