6-250 7SA522 Manual
C53000-G1176-C119-2
$ :$9()250&$3785(). Normally the reference instant is the occurrence of de-
vice fault detection, i.e. the fault detection of any protection function is allocated with
the time stamp 0. The fault detection can also be the storage criterion (6DYHZ
3LFNXS) or the device trip command (6DYHZ75,3) can be the storage criterion.
The device trip command can also be used as reference time (6WDUWZ75,3); in
this case it is also the storage criterion.
A fault event starts with the fault detection of any protection function and ends with the
reset of the last fault detection. Usually this is also the extent of a fault recording (ad-
dress $ 6&23(2) :$9()250'$7$ = )DXOWHYHQW). If automatic reclosure is
implemented, the entire system disturbance — possibly with several reclose
attempts — up to the ultimate fault clearance can be stored (address $ 6&23(2)
:$9()250'$7$ = 3RZHU6\VWHPIDXOW). This facilitates the representation of the
entire system fault history, but also consumes storage capacity during the auto-reclos-
ure dead time(s).
The actual storage time encompasses the pre-fault time 35(75,*7,0( (address
) ahead of the reference instant, the normal recording time and the post-fault time
32675(&7,0( (address ) after the storage criterion has reset. The maximum
permissible storage period per fault recording 0$;/(1*7+ is set in address . A
maximum recording time of 5 s is available per fault recording. In total up to 8 fault
records with a total recording time of max. 15 s can be stored.
The fault recording can also be triggered via a binary input, via the keypad on the front
of the device or with a PC via the operation or service interface. The storage is then
dynamically triggered. The length of the fault recording is set in address  %LQ,Q
&$377,0( (maximum length however is 0$;/(1*7+, address . The pre-
and post-fault times are additive. If the time for the binary input is set to , the duration
of the storage is as long as the binary input is initiated (static), the maximum length
however still is 0$;/(1*7+ (address ).
6.18.5 Settings
Addr. Setting Title Setting Options Default Setting Comments
402A WAVEFORM CAP-
TURE
Save with Pickup
Save with TRIP
Start with TRIP
Save with Pickup Waveform Capture
403A SCOPE OF WAVE-
FORM DATA
Fault event
Power System fault
Fault event Scope of Waveform Data
410 MAX. LENGTH 0.30..5.00 sec 1.00 sec Max. length of a Waveform Cap-
ture Record
411 PRE. TRIG. TIME 0.05..0.50 sec 0.10 sec Captured Waveform Prior to
Trigger
412 POST REC. TIME 0.05..0.50 sec 0.10 sec Captured Waveform after Event
415 BinIn CAPT.TIME 0.10..5.00 sec 0.50 sec Capture Time via Binary Input