6.1.3.1 Settings
Addr. Setting Title Setting Options Default Setting Comments
1103 FullScaleVolt. 1.0..1200.0 kV 400.0 kV Measurement: Full Scale
Voltage (100%)
1104 FullScaleCurr. 10..5000 A 1000 A Measurement: Full Scale Cur-
rent (100%)
1105 Line Angle 30..89 ° 85 ° Line Angle
1110 x’ 0.005..6.500 Ohm / km 0.150 Ohm / km x’ - Line Reactance per length
unit
1111 Line Length 1.0..1000.0 km 100.0 km Line Length
1112 x’ 0.005..10.000 Ohm / mile 0.242 Ohm / mile x’ - Line Reactance per length
unit
1113 Line Length 0.6..650.0 Miles 62.1 Miles Line Length
1116 RE/RL(Z1) -.33..7.00 1.00 Zero seq. comp. factor RE/RL
for Z1
1117 XE/XL(Z1) -.33..7.00 1.00 Zero seq. comp. factor XE/XL for
Z1
1118 RE/RL(Z1B...Z5) -.33..7.00 1.00 Zero seq. comp.factor RE/RL for
Z1B...Z5
1119 XE/XL(Z1B...Z5) -.33..7.00 1.00 Zero seq. comp.factor XE/XL for
Z1B...Z5
1120 K0 (Z1) 0.000..4.000 1.000 Zero seq. comp. factor K0 for
zone Z1
1121 Angle K0(Z1) -135.00..135.00 ° 0.00 ° Zero seq. comp. angle for zone
Z1
1122 K0 (> Z1) 0.000..4.000 1.000 Zero seq.comp.factor K0,higher
zones >Z1
1123 AngleI K0(> Z1) -135.00..135.00 ° 0.00 ° Zero seq. comp. angle, higher
zones >Z1
1126 RM/RL ParalLine 0.00..8.00 0.00 Mutual Parallel Line comp. ratio
RM/RL
1127 XM/XL ParalLine 0.00..8.00 0.00 Mutual Parallel Line comp. ratio
XM/XL
1128 RATIO Par. Comp 50..95 % 85 % Neutral current RATIO Parallel
Line Comp
1130 PoleOpenCurrent 0.05..1.00 A 0.10 A Pole Open Current Threshold
1131 PoleOpenVoltage 2..70 V 30 V Pole Open Voltage Threshold
1132 SI Time all Cl. 0.01..30.00 sec 0.05 sec Seal-in Time after ALL closures
1134 Line Closure Manual Close BI only
Current OR Voltage or
Manual close BI
CBaux OR Current or
Manual close BI
Current flow or Manual close
BI
Manual Close BI
only
Recognition of Line Closures