Control During Operation
7-197SA522 Manual
C53000-G1176-C119-2
7.1.3.3 Retrieval and Resetting of User Defined Pulse Metered Values (PMV)
In the 7SA522 it is possible to define pulse metered values with the user definable log-
ic (CFC) (see Section 5.3).
If such pulse metered values were defined during the configuration of the device, they
can — with password No. 5 — be reset to 0:
From the
Device Front
With the device ready for operation, first press the key. The 0$,10(18 appears.
Use the key to select the menu item 0HDVXUHPHQW, and switch to the list of meas-
ured values using the key. The 0($685(0(17 selection appears.
There select with key the menu item 5HVHW and switch to the 5(6(7 option with
the key (refer to Figure 7-22).
Figure 7-22 Resetting of pulse metered values on the device front
With the keys and you may page up and down in the table, if several positions
are available.
If one of the memories should be reset, mark it with the keys and , and then se-
lect it by pressing the key.
A prompt to enter the password No. 5 (for individual parameters) appears. After entry
of the password and confirmation with , the reset command is executed.
Press the key. The display confirms the entry with “&KDQJH2.&RQWLQXH”.
Confirm again by pressing the key. The resetting is complete.
If further counters are available, they can be reset in the same manner.
With the key, a return to the level 0HDVXUHPHQW is possible, with the key, you
may jump to the 0$,10(18.
From PC with
DIGSI
®
4
Double click on 0HDVXUHPHQW (Figure 7-2). Select 2WKHU and then 8VHU'HILQHG.
By double clicking on an entry in the list view in the right side of the window, the limit
values are loaded. Mark the number of the value that is to be changed. With the
right
mouse button, open the context menu and click on 6HW. A password inquiry (password
for individual settings) occurs. Next, the dialogue field 6HW"""""9DOXH is opened.
Enter the desired value in the entry field, if applicable, the value . Then click on 2..
The new value is transferred to the relay.
MENU
5HVHW

0HWHUUHV !
ENTER
ENTER
ENTER
ENTER
MENU
:

Table of Contents

Other manuals for Siemens siprotec 7SA522

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens siprotec 7SA522 and is the answer not in the manual?

Siemens siprotec 7SA522 Specifications

General IconGeneral
BrandSiemens
Modelsiprotec 7SA522
CategoryProtection Device
LanguageEnglish

Related product manuals