Control During Operation
7-18 7SA522 Manual
C53000-G1176-C119-2
swer “1R” is marked, and confirm with the key. If the value is to be modified once
more, mark “$ERUW”, confirm this with the key and re-enter the value.
From PC with
DIGSI
®
4
Set points are only available in online–mode. The metered value groups are found un-
der 0HDVXUHPHQW (Figure 7-2) with a double click. Select 2WKHU and then 6HW
3RLQWV0HDVXUHG9DOXHVFigure 7-21).
By double clicking on an entry in the list view in the right side of the window, the limit
values are loaded. Mark the number of the value that is to be changed. With the
right
mouse button, open the context menu and click on 6HW, as shown in Figure 7-21. A
password inquiry (password No 5 for individual settings) occurs. Next, the dialog field
6HW0HWHUHG9DOXH is opened. Enter the desired value in the entry field. Then click
on 2..
The entered value is transferred to the device and the display within the window in Fig-
ure 7-21 is updated.
Figure 7-21 Set Points in DIGSI
®
4
ENTER
ENTER
: