Functions
6-377SA522 Manual
C53000-G1176-C119-2
During three phase faults the fault detection of all three phase-phase loops usually oc-
curs. In this case the three phase-phase loops are evaluated. If earth fault detection
also occurs, the phase-earth loops are also evaluated.
Correction of meas-
ured values for
Parallel Lines
During earth faults on parallel lines, the impedance values calculated by means of the
loop equations are influenced by the coupling of the earth impedance of the two con-
ductor systems (Figure 6-23). Unless special measures are employed, this results in
measuring errors in the result of the impedance computation. A parallel line compen-
sation may therefore be activated. In this manner the earth current of the parallel line
is taken into consideration by the line equation and thereby allows for compensation
of the coupling influence. The earth current of the parallel line must be connected to
the device for this purpose. The loop equation is then modified as shown below, refer
also to Figure 6-21
where I
EP
is the earth current of the parallel line and the ratio Z
M
/Z
L
is a constant line
parameter, resulting from the geometry of the double circuit line and the nature of the
Table 6-2 Evaluation of the measured loops during multiple loop fault detection
Fault detection
Loops
evaluated
Loop(s)
Setting
Parameter 1221
L1–E, L2–E, L1–L2
L2–E, L3–E, L2–L3
L1–E, L3–E, L3–L1
L2–E, L1–L2
L3–E, L2–L3
L1–E, L3–L1
3K(IDXOWV
%ORFNOHDGLQJ
L1–E, L2–E, L1–L2
L2–E, L3–E, L2–L3
L1–E, L3–E, L3–L1
L1–E, L1–L2
L2–E, L2–L3
L3–E, L3–L1
3K(IDXOWV
%ORFNODJJLQJ
L1–E, L2–E, L1–L2
L2–E, L3–E, L2–L3
L1–E, L3–E, L3–L1
L1–E, L2–E, L1–L2
L2–E, L3–E, L2–L3
L1–E, L3–E, L3–L1
3K(IDXOWV
$OOORRSV
L1–E, L2–E, L1–L2
L2–E, L3–E, L2–L3
L1–E, L3–E, L3–L1
L1–L2
L2–L3
L3–L1
3K(IDXOWV
ORRSVRQO\
L1–E, L2–E, L1–L2
L2–E, L3–E, L2–L3
L1–E, L3–E, L3–L1
L1–E, L2–E
L2–E, L3–E
L1–E, L3–E
3K(IDXOWV
(ORRSVRQO\
I
L3
Z
L
I
E
Z
E
I
EP
Z
M
U
=
L3–E
I
L3
Z
L
I
E
Z
L
Z
E
Z
L
-------
I
EP
Z
L
Z
M
Z
L
-------
⋅⋅
U
L3–E
=⋅⋅

Table of Contents

Other manuals for Siemens siprotec 7SA522

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens siprotec 7SA522 and is the answer not in the manual?

Siemens siprotec 7SA522 Specifications

General IconGeneral
BrandSiemens
Modelsiprotec 7SA522
CategoryProtection Device
LanguageEnglish

Related product manuals