Introduction
1-97SA522 Manual
C53000-G1176-C119-2
High Current Fast
Switch-on-to-Fault
Protection
fast tripping for switch-on-to-fault conditions;
selectable for manual closure or following each closure of the circuit breaker;
with integrated line energization detection.
Automatic
reclosure
(optional)
for reclosure after single-pole, three-pole or single and three-pole tripping;
single or multiple reclosure (up to 8 reclosure attempts);
with separate action times for every reclosure attempt, optionally without action
times;
with separate dead times after single-pole and three-pole tripping, separate for the
first four reclosure attempts;
controlled optionally by protection start with separate dead times after single, two
and three-pole starting
Synchronism and
voltage check
(dead-line / dead-
bus check)
(optional)
checking synchronization conditions before reclosure after three-pole switching;
fast measuring of voltage difference U diff of the phase angle difference
ϕ diff and
the frequency difference f diff;
alternative check of dead-line / dead-bus before reclosure;
switching under asynchronous network conditions with advance calculation of the
synchro-time possible;
adjustable minimum and maximum voltage;
check synchronism or dead-line / dead-bus also before manual closure of the circuit
breaker possible, with separate limit values;
measurement via transformer also possible;
measuring voltages optionally phase-phase or phase-earth
Overvoltage
Protection
(optional)
Overvoltage detection of each phase-earth voltage with common time delay;
separate measuring system with a separate time delay, for the zero sequence volt-
age, or any other single-phase voltage;
the reset ratio of the single-phase (zero sequence) voltage protection can be set;
command transfer to the remote line end is possible.
Fault Location Initiated by trip command or reset of the fault detection;
computation of the distance to fault with dedicated measured value registers;
fault location output in ohm, kilometers or miles and % of line length;
parallel line compensation can be selected;
load compensation available.
Circuit breaker
failure protection
(optional)
with independent current stages for monitoring current flow through every pole of
the circuit breaker;
with independent monitoring time steps for single-pole and three-pole tripping;
start by trip command of every internal protection function;
start by external trip functions possible;