Functions
6-176 7SA522 Manual
C53000-G1176-C119-2
3463 2.AR 1p allowed YES
NO
NO 1pole TRIP allowed
3464 2.AR Tdead 1Flt 0.01..1800.00 sec 1.20 sec Dead time after 1phase faults
3465 2.AR Tdead 2Flt 0.01..1800.00 sec 1.20 sec Dead time after 2phase faults
3466 2.AR Tdead 3Flt 0.01..1800.00 sec 0.50 sec Dead time after 3phase faults
3467 2.AR Tdead1Trip 0.01..1800.00 sec 1.20 sec Dead time after 1pole trip
3468 2.AR Tdead3Trip 0.01..1800.00 sec 0.50 sec Dead time after 3pole trip
3469 2.AR: Tdead EV. 0.01..1800.00 sec 1.20 sec Dead time after evolving fault
3470 2.AR: CB? CLOSE YES
NO
NO CB ready interrogation before
reclosing
3471 2.AR SynRequest YES
NO
NO Request for synchro-check after
3pole AR
3472 3.AR: START YES
NO
NO AR start allowed in this cycle
3473 3.AR: T-ACTION 0.01..300.00 sec 0.20 sec Action time
3474 3.AR 1p allowed YES
NO
NO 1pole TRIP allowed
3475 3.AR Tdead 1Flt 0.01..1800.00 sec 1.20 sec Dead time after 1phase faults
3476 3.AR Tdead 2Flt 0.01..1800.00 sec 1.20 sec Dead time after 2phase faults
3477 3.AR Tdead 3Flt 0.01..1800.00 sec 0.50 sec Dead time after 3phase faults
3478 3.AR Tdead1Trip 0.01..1800.00 sec 1.20 sec Dead time after 1pole trip
3479 3.AR Tdead3Trip 0.01..1800.00 sec 0.50 sec Dead time after 3pole trip
3480 3.AR: Tdead EV. 0.01..1800.00 sec 1.20 sec Dead time after evolving fault
3481 3.AR: CB? CLOSE YES
NO
NO CB ready interrogation before
reclosing
3482 3.AR SynRequest YES
NO
NO Request for synchro-check after
3pole AR
3483 4.AR: START YES
NO
NO AR start allowed in this cycle
3484 4.AR: T-ACTION 0.01..300.00 sec 0.20 sec Action time
3485 4.AR 1p allowed YES
NO
NO 1pole TRIP allowed
3486 4.AR Tdead 1Flt 0.01..1800.00 sec 1.20 sec Dead time after 1phase faults
3487 4.AR Tdead 2Flt 0.01..1800.00 sec 1.20 sec Dead time after 2phase faults
3488 4.AR Tdead 3Flt 0.01..1800.00 sec 0.50 sec Dead time after 3phase faults
3489 4.AR Tdead1Trip 0.01..1800.00 sec 1.20 sec Dead time after 1pole trip
3490 4.AR Tdead3Trip 0.01..1800.00 sec 0.50 sec Dead time after 3pole trip
3491 4.AR: Tdead EV. 0.01..1800.00 sec 1.20 sec Dead time after evolving fault
3492 4.AR: CB? CLOSE YES
NO
NO CB ready interrogation before
reclosing
Addr. Setting Title Setting Options Default Setting Comments