Functions
6-2057SA522 Manual
C53000-G1176-C119-2
Figure 6-102 Breaker failure protection with phase segregated initiation — example for initia-
tion by an external protection device with release by a fault detection signal
Figure 6-103 Breaker failure protection with phase segregated initiation — example for initia-
tion by an external protection device with release by a separate set of trip contacts
Initiation of a single-phase, e.g. “Start L1 only” is valid when the starting input (= trip
command of any feeder protection) appears for only this phase and current flow is de-
tected in at least this phase. If current flow is not detected, the auxiliary contact posi-
tion can be interrogated according to Figure 6-100, dependent on the setting (&KN
%5.&217$&7 = <HV).
The auxiliary contact criterion is also processed for each individual breaker pole. If
however the breaker auxiliary contacts are not available for each individual breaker
pole, then a single-pole trip command is assumed to be executed only once the series
connection of the normally open (NO) auxiliary contacts is interrupted. This informa-
tion is provided to the breaker fail protection by the function control of the device (refer
to Section 6.14.2 ) .
The three-phase starting signal “Start L123” is generated if trip signals appear in more
than one pole (regardless from which protection function). Phase segregated initiation
is then blocked. The input “Start without I” (e.g. from Buchholz protection) operates in
three-phase mode as well. The function is the same as with common phase initiation.
7SA522
Trip L1
Trip L2
Trip L3
Pick-up
L+
external
prot. device
L–
>BF Start L1
>BF Start L2
>BF Start L3
>BF Release
7SA522
Trip L1
L+
external
prot. device
L–
>BF Start L1
Trip L1
Trip L2 >BF Start L2
Trip L2
Trip L3 >BF Start L3
Trip L3
>BF Release

Table of Contents

Other manuals for Siemens siprotec 7SA522

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens siprotec 7SA522 and is the answer not in the manual?

Siemens siprotec 7SA522 Specifications

General IconGeneral
BrandSiemens
Modelsiprotec 7SA522
CategoryProtection Device
LanguageEnglish

Related product manuals