Installation and Commissioning
8-457SA522 Manual
C53000-G1176-C119-2
The first time a button is clicked in the Action column to send a message, Password
No. 6 (for hardware test menus) is requested, After correct input of the password, mes-
sages can be individually transmitted. To send a message, click on the Action button
of the corresponding line. The corresponding message is then sent. The message can
be read in the Event Log of the SIPROTEC
®
device and in the SCADA.
The capability of sending further messages remains until the dialog box is closed.
Ending the
Procedure
To end the System Interface Test, click on Close. The device is briefly out of service
while the start-up routine is executed. The dialog box closes.
Note:
When the System Interface Test is terminated, the device changes to the start-up
mode (reboots). All hardware components are returned to the operating conditions de-
termined by the substation settings; however, all message buffers are deleted. Any
data required from the message buffers must therefor be read before the test is
closed.

Table of Contents

Other manuals for Siemens siprotec 7SA522

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens siprotec 7SA522 and is the answer not in the manual?

Siemens siprotec 7SA522 Specifications

General IconGeneral
BrandSiemens
Modelsiprotec 7SA522
CategoryProtection Device
LanguageEnglish

Related product manuals