Appendix
A-157SA522 Manual
C53000-G1176-C119-2
Figure 1-10 Current connections to three current transformers and a separate neutral current
transformer (summation transformer) for earth current — preferred for effectively
or low-resistive earthed networks
Important! Cable shield grounding must be done on the cable side!
Note: Change of Address 0201 setting changes polarity of 3I
0
Current
Input, i.e. terminal Q7 must be connected to that CT terminal point-
ing in the same direction as the starpoint of the phase current CTs
(towards “Line side” in this diagramm)
Panel surface mounted
Flush mounted/cubicle
L1 L2 L3
k
l
I
4
I
L1
I
L2
I
L3
Q1
Q3
Q5
Q2
Q4
Q6
Q7Q8
k
l
25
24
23
47
50
49
48
22
7SA522
Housing size
1
/
2
Panel surface mounted
Flush mounted/cubicle
L1 L2 L3
k
l
I
4
I
L1
I
L2
I
L3
Q1
Q3
Q5
Q2
Q4
Q6
Q7Q8
k
l
50
49
48
97
100
99
98
47
7SA522
Housing size
1
/
1
Important! Cable shield grounding must be done on the cable side!
Note: Change of Address 0201 setting changes polarity of 3I
0
Current
Input, i.e. terminal Q7 must be connected to that CT terminal point-
ing in the same direction as the starpoint of the phase current CTs
(towards “Line side” in this diagramm)

Table of Contents

Other manuals for Siemens siprotec 7SA522

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens siprotec 7SA522 and is the answer not in the manual?

Siemens siprotec 7SA522 Specifications

General IconGeneral
BrandSiemens
Modelsiprotec 7SA522
CategoryProtection Device
LanguageEnglish

Related product manuals