Appendix
B-25
7SA522 Manual
C53000-G1176-C119-2
1310 >Earth Fault O/C Instantaneous trip
(>EF InstTRIP)
Earth fault
overcurrent
SP ON
OFF
ON
OFF
LED BI BO 166 10 1 GI
1311 >E/F Teleprotection ON (>EF Tele-
prot.ON)
Teleprotec-
tion for Earth
fault overcurr.
SP * * LED BI BO
1312 >E/F Teleprotection OFF (>EF Tele-
protOFF)
Teleprotec-
tion for Earth
fault overcurr.
SP * * LED BI BO
1313 >E/F Teleprotection BLOCK (>EF
TeleprotBLK)
Teleprotec-
tion for Earth
fault overcurr.
SP ON
OFF
* LED BI BO 166 13 1 GI
1318 >E/F Carrier RECEPTION, Channel
1 (>EF Rec.Ch1)
Teleprotec-
tion for Earth
fault overcurr.
SP on
off
on LED BI BO 166 18 1 GI
1319 >E/F Carrier RECEPTION, Channel
2 (>EF Rec.Ch2)
Teleprotec-
tion for Earth
fault overcurr.
SP on
off
on LED BI BO 166 19 1 GI
1320 >E/F Unblocking: UNBLOCK, Chan-
nel 1 (>EF UB ub 1)
Teleprotec-
tion for Earth
fault overcurr.
SP ON
OFF
ON LED BI BO 166 20 1 GI
1321 >E/F Unblocking: BLOCK, Channel 1
(>EF UB bl 1)
Teleprotec-
tion for Earth
fault overcurr.
SP ON
OFF
ON LED BI BO 166 21 1 GI
1322 >E/F Unblocking: UNBLOCK, Chan-
nel 2 (>EF UB ub 2)
Teleprotec-
tion for Earth
fault overcurr.
SP ON
OFF
ON LED BI BO 166 22 1 GI
1323 >E/F Unblocking: BLOCK, Channel 2
(>EF UB bl 2)
Teleprotec-
tion for Earth
fault overcurr.
SP ON
OFF
ON LED BI BO 166 23 1 GI
1324 >E/F BLOCK Echo Signal (>EF
BlkEcho)
Teleprotec-
tion for Earth
fault overcurr.
SP ON
OFF
ON LED BI BO 166 24 1 GI
1331 Earth fault protection is switched
OFF (E/F Prot. OFF)
Earth fault
overcurrent
OUT ON
OFF
* LED BO 166 31 1 GI
1332 Earth fault protection is BLOCKED
(E/F BLOCK)
Earth fault
overcurrent
OUT ON
OFF
ON
OFF
LED BO 166 32 1 GI
1333 Earth fault protection is ACTIVE (E/F
ACTIVE)
Earth fault
overcurrent
OUT * * LED BO 166 33 1 GI
1345 Earth fault protection PICKED UP
(EF Pickup)
Earth fault
overcurrent
OUT *
OFF
M LED BO 166 45 2 GI
1354 E/F 3I0>>> PICKED UP (EF
3I0>>>Pickup)
Earth fault
overcurrent
OUT * ON LED BO
1355 E/F 3I0>> PICKED UP (EF 3I0>>
Pikkup)
Earth fault
overcurrent
OUT * ON LED BO
1356 E/F 3I0> PICKED UP (EF 3I0>
Pikkup)
Earth fault
overcurrent
OUT * ON LED BO
1357 E/F 3I0p PICKED UP (EF 3I0p
Pikkup)
Earth fault
overcurrent
OUT * ON LED BO
1358 E/F picked up FORWARD (EF for-
ward)
Earth fault
overcurrent
OUT * ON LED BO 166 58 2
F.No. Description Function Type of Infor-
mation
Log-Buffers Configurable in Matrix IEC 60870-5-103
Event Log On/Off
Trip (Fault) Log On/Off
Ground Fault Log On/Off
Marked in Oscill. Record
LED
Binary Input
Function Key
Binary Output
Event Log
Type
Information-No
Data Unit (ASDU)
General Interrogation