Appendix
B-29
7SA522 Manual
C53000-G1176-C119-2
2781 AR: Auto-reclose is switched off (AR
off)
Automatic
Reclosure
OUT ON
OFF
* LED BO 40 81 1 GI
2782 AR: Auto-reclose is switched on (AR
on)
Automatic
Reclosure
IntSP * * LED BO 128 16 1 GI
2783 AR: Auto-reclose is blocked (AR is
blocked)
Automatic
Reclosure
OUT ON
OFF
* LED BO 40 83 1 GI
2784 AR: Auto-reclose is not ready (AR
not ready)
Automatic
Reclosure
OUT * ON LED BO 128 130 1 GI
2787 AR: Circuit breaker not ready (CB
not ready)
Automatic
Reclosure
OUT * * LED BO 40 87 1
2788 AR: CB ready monitoring window
expired (AR T-CBreadyExp)
Automatic
Reclosure
OUT * ON LED BO 40 88 2
2796 AR: Auto-reclose ON/OFF via BI (AR
on/off BI)
Automatic
Reclosure
IntSP * * LED BO
2801 AR in progress (AR in progress) Automatic
Reclosure
OUT * ON LED BO 40 101 2 GI
2809 AR: Start-signal monitoring time
expired (AR T-Start Exp)
Automatic
Reclosure
OUT * ON LED BO 40 174 1
2810 AR: Maximum dead time expired
(AR TdeadMax Exp)
Automatic
Reclosure
OUT * ON LED BO 40 175 1
2818 AR: Evolving fault recognition (AR
evolving Flt)
Automatic
Reclosure
OUT * ON LED BO 40 118 2 GI
2820 AR is set to operate after 1p trip only
(AR Program1pole)
Automatic
Reclosure
OUT * * LED BO 40 143 1
2821 AR dead time after evolving fault (AR
Td. evol.Flt)
Automatic
Reclosure
OUT * ON LED BO 40 197 2
2839 AR dead time after 1pole trip running
(AR Tdead 1pTrip)
Automatic
Reclosure
OUT * ON LED BO 40 148 2 GI
2840 AR dead time after 3pole trip running
(AR Tdead 3pTrip)
Automatic
Reclosure
OUT * ON LED BO 40 149 2 GI
2841 AR dead time after 1phase fault run-
ning (AR Tdead 1pFlt)
Automatic
Reclosure
OUT * ON LED BO 40 150 2 GI
2842 AR dead time after 2phase fault run-
ning (AR Tdead 2pFlt)
Automatic
Reclosure
OUT * ON LED BO 40 151 2 GI
2843 AR dead time after 3phase fault run-
ning (AR Tdead 3pFlt)
Automatic
Reclosure
OUT * ON LED BO 40 154 2 GI
2844 AR 1st cycle running (AR 1stCyc.
run.)
Automatic
Reclosure
OUT * ON LED BO 40 155 2 GI
2845 AR 2nd cycle running (AR 2ndCyc.
run.)
Automatic
Reclosure
OUT * ON LED BO 40 157 2 GI
2846 AR 3rd cycle running (AR 3rdCyc.
run.)
Automatic
Reclosure
OUT * ON LED BO 40 158 2 GI
2847 AR 4th or higher cycle running (AR
4thCyc. run.)
Automatic
Reclosure
OUT * ON LED BO 40 159 2 GI
2848 AR cycle is running in ADT mode
(AR ADT run.)
Automatic
Reclosure
OUT * ON LED BO 40 130 2 GI
2851 AR: Close command (AR CLOSE
Cmd.)
Automatic
Reclosure
OUT * ON M LED BO 40 128 1
F.No. Description Function Type of Infor-
mation
Log-Buffers Configurable in Matrix IEC 60870-5-103
Event Log On/Off
Trip (Fault) Log On/Off
Ground Fault Log On/Off
Marked in Oscill. Record
LED
Binary Input
Function Key
Binary Output
Event Log
Type
Information-No
Data Unit (ASDU)
General Interrogation

Table of Contents