Appendix
B-39
7SA522 Manual
C53000-G1176-C119-2
4052 Dis. Teleprotection is switched OFF
(Dis.Telep. OFF)
Teleprotec-
tion for Dis-
tance prot.
OUT ON
OFF
* LED BO
4054 Dis. Telep. Carrier signal received
(Dis.T.Carr.rec.)
Teleprotec-
tion for Dis-
tance prot.
OUT * * LED BO 128 77 2
4055 Dis. Telep. Carrier CHANNEL FAIL-
URE (Dis.T.Carr.Fail)
Teleprotec-
tion for Dis-
tance prot.
OUT * * LED BO 128 39 1 GI
4056 Dis. Telep. Carrier SEND signal
(Dis.T.SEND)
Teleprotec-
tion for Dis-
tance prot.
OUT on on LED BO 128 76 2
4057 Dis. Telep. Carrier SEND signal, L1
(Dis.T.SEND L1)
Teleprotec-
tion for Dis-
tance prot.
OUT * * LED BO
4058 Dis. Telep. Carrier SEND signal, L2
(Dis.T.SEND L2)
Teleprotec-
tion for Dis-
tance prot.
OUT * * LED BO
4059 Dis. Telep. Carrier SEND signal, L3
(Dis.T.SEND L3)
Teleprotec-
tion for Dis-
tance prot.
OUT * * LED BO
4060 Dis.Tele.Blocking: Send signal with
jump (DisJumpBlocking)
Teleprotec-
tion for Dis-
tance prot.
OUT * * LED BO 29 60 2
4068 Dis. Telep. Transient Blocking
(Dis.T.Trans.Blk)
Teleprotec-
tion for Dis-
tance prot.
OUT * ON LED BO 29 68 2
4070 Dis. Tele.Blocking: carrier STOP sig-
nal (Dis.T.BL STOP)
Teleprotec-
tion for Dis-
tance prot.
OUT * ON LED BO 29 70 2
4080 Dis. Tele.Unblocking: FAILURE
Channel 1 (Dis.T.UB Fail1)
Teleprotec-
tion for Dis-
tance prot.
OUT on
off
* LED BO 29 80 1 GI
4081 Dis. Tele.Unblocking: FAILURE
Channel 2 (Dis.T.UB Fail2)
Teleprotec-
tion for Dis-
tance prot.
OUT on
off
* LED BO 29 81 1 GI
4082 DisTel Blocking: carrier STOP sig-
nal, L1 (Dis.T.BL STOPL1)
Teleprotec-
tion for Dis-
tance prot.
OUT * * LED BO
4083 DisTel Blocking: carrier STOP sig-
nal, L2 (Dis.T.BL STOPL2)
Teleprotec-
tion for Dis-
tance prot.
OUT * * LED BO
4084 DisTel Blocking: carrier STOP sig-
nal, L3 (Dis.T.BL STOPL3)
Teleprotec-
tion for Dis-
tance prot.
OUT * * LED BO
4164 Power Swing detected (Power
Swing)
Power Swing OUT ON
OFF
ON
OFF
LED BO 29 164 1 GI
4166 Power Swing TRIP command (Pow.
Swing TRIP)
Power Swing OUT ON ON LED BO 29 166 1
4167 Power Swing detected in L1 (Pow.
Swing L1)
Power Swing OUT ON
OFF
ON
OFF
LED BO
F.No. Description Function Type of Infor-
mation
Log-Buffers Configurable in Matrix IEC 60870-5-103
Event Log On/Off
Trip (Fault) Log On/Off
Ground Fault Log On/Off
Marked in Oscill. Record
LED
Binary Input
Function Key
Binary Output
Event Log
Type
Information-No
Data Unit (ASDU)
General Interrogation