SIPROTEC
®
4 Devices
4-237SA522 Manual
C53000-G1176-C119-2
CFC SIPROTEC
®
4 device information can be connected in a user-specified manner using
the programmable logic components of the DIGSI
®
4 CFC. For example, the user can
implement interlocking checks, create grouped messages, or derive limit value viola-
tion messages.
Information can be both a source and a destination in combined CFC editing. The spe-
cific logic’s inputs, e.g. the individual messages that are to be combined to form a
grouped message, must be marked in the Destination C column. The logic’s output,
the grouped message in this example, is derived from the Source C column.
Viewing the Config-
uration on the
Operating Panel
The configuration can be seen on the operating panel of the SIPROTEC
®
4 device.
• In the main menu, select 6HWWLQJV → 0DVNLQJ,2.
.
• In the next menu, select 0DVNLQJ,2 → e.g. %LQDU\,QSXWV.
.
Figure 4-18 Reading the configuration using the operator control panel, example assignment
of binary input 2
0$6.,1*,2
!%LQDU\,QSXWV²!
!/('²!
%,1$5<,13876
!%LQDU\,QSXW²!²
!%LQDU\,QSXW²!²