Technical Data
10-4 7SA6 Manual
C53000-G1176-C156
-7SA641∗–∗A/J/M/P 13(allocatable)
-7SA641
∗–∗B/K 20(allocatable)
-7SA642
∗–∗A/J/M/R 21(allocatable)
-7SA642
∗–∗B/K/N/S 29(allocatable)
-7SA642
∗–∗C/L 33(allocatable)
Nominal voltage 24 VDC to 250 VDC in 3 ranges, bipolar
Switching thresholds adjustable with jumpers
– for nominal voltages 24/48 VDC U
pick-up
≥ 19 VDC
60/110/125 VDC U
drop-off
≤ 14 VDC
– for nominal voltages 110/125/ U
pick-up
≥ 88 VDC
220/250 VDC U
drop-off
≤ 66 VDC
– for nominal voltages 220/250 VDC U
pick-up
≥ 176 VDC
U
drop-off
≤ 117 VDC
Current consumption, energized approx. 1.8 mA
independent of the control voltage
Maximum permissible voltage 300 VDC
Impulse filter on input 220 nF coupling capacity at 220 V
with recovery time >60 ms