Technical Data
10-57SA6 Manual
C53000-G1176-C156
Binary Outputs Output relay (see also General Diagrams in Appendix A, Section A.2)
Number and Information acc. to the order variant
(allocatable)
Alarm relay/Live Status contact
1
) 1 with NC contact or NO contact
(switch selectable)
Switching capability MAKE 1000 W/VA
BREAK 30 VA
40 W resistive
25 W for L/R
≤ 50 ms
Switching voltage 250 V
Permissible current per contact 5 A continuous
30 A for 0.5 s
Order Variant
UL-listed
NO
Contact
(normal)
1)
NO
Contact
(fast)
1)
NO/NC
(switch
selectable)
1)
NO
Contact
(high
–speed)
1)
Power
Relay
2)
7SA610∗–∗A/E/J x 7 – 1 – –
7SA610∗–∗B/F/K x 5 – – – –
7SA6∗1∗–∗A/E/J x 7 7 2 – –
7SA6∗1∗–∗B/F/K x 8 – – – 4
7SA6∗1∗–∗M/N/P x 7 3 1 5 –
7SA6∗2∗–∗A/E/J x 14 7 3 – –
7SA6∗2∗–∗B/F/K x 21 7 4 – –
7SA6∗2∗–∗M/P/R x 14 3 2 5 –
7SA6∗2∗–∗N/Q/S x 21 3 3 5 –
7SA6∗2∗–∗C/G/L x 11 – – – 8
7SA613∗–∗A–1473––
7SA613∗–∗M–14325–
Switching capability MAKE
BREAK
1000 W/VA
30 VA
40 W ohmic
25 W/VA for L/R
≤ 50 ms
1000 W/VA
1000 W/VA
–
–
–
–
Switching voltage 250 V 250 V
Permissible current per contact/
pulse current
5 A permanent
30 A for 0.5 s 30 A for
0.5 s
Total permissible current
on common paths
5 A permanent
30 A for 0.5 s
–
–
Max. switching
capability for 30 s
for 48 V to
250 V
for 24 V
–
–
1000 W
500 W
Permissible relative closing time
–1%
Operating time, approx.
8ms 5ms 8ms 1ms –