Technical Data
10-77SA6 Manual
C53000-G1176-C156
shielded data cable
– Test voltage 500 V; 50 Hz
– Transmission speed min. 4800 Baud; max. 115200 Baud
factory setting: 38400 Baud
– Maximum transmission distance max. 1km
Optical fibre
– Connector Type ST–connector
for flush mounted case rear panel, mounting location “C”
for surface mounted case at the inclined housing on the case bottom
–Opticalwavelength
λ = 820 nm
– Laser class 1 acc. EN 60825–1/ –2 using glass fibre 50/125 µm or
using glass fibre 62.5/125 µm
– Permissible optical signal attenuation max. 8 dB using glass fibre 62.5/125 µm
– Maximum transmission distance 1.5 km (0.93 miles)
– Character idle state selectable; factory setting: “Light off”
System (SCADA)
Interface
(optional)
RS232/RS485/Optical floating interface for data transfer
Profibus RS485/Profibus Optical to a master terminal
acc. to ordered version
RS232
– Connection for flush mounted case rear panel, mounting location “B”
9-pin DSUB socket
for surface mounted case at the inclined housing on the case bottom
9-pin DSUB socket
– Test voltage 500 V; 50 Hz
– Transmission speed min. 4800 Bd, max. 38400 Bd
factory setting: 19200 Bd
– Maximum transmission distance 15 m (50 ft)
RS485
– Connection for flush mounted case rear panel, mounting location “B”
9-pin DSUB socket
for surface mounted case at the inclined housing on the case bottom
9-pin DSUB socket
– Test voltage 500 V, 50 Hz
– Transmission speed min. 4800 Bd, max. 38400 Bd
factory setting: 19200 Bd
– Maximum transmission distance 1000 m (3280 ft)
– Bridging distance max. 1 km
Profibus RS
485
– Connection for flush mounted case rear panel, mounting location “B”
9-pin DSUB socket
for surface mounted case at the inclined housing on the case bottom
9-pin DSUB socket