Appendix
B-28
7SA6 Manual
C53000-G1176-C156-2
533 Primary fault current IL1 (IL1 =) Power System
Data 2
OUT * ON
OFF
150 177 4
534 Primary fault current IL2 (IL2 =) Power System
Data 2
OUT * ON
OFF
150 178 4
535 Primary fault current IL3 (IL3 =) Power System
Data 2
OUT * ON
OFF
150 179 4
536 Relay Definitive TRIP (Definitive TRIP) Power System
Data 2
OUT ON ON * LED BO 150 180 2
545 Time from Pickup to drop out (PU Time) Power System
Data 2
OUT
546 Time from Pickup to TRIP (TRIP Time) Power System
Data 2
OUT
560 Single-phase trip was coupled 3phase
(Trip Coupled 3p)
Power System
Data 2
OUT * ON LED BO 150 210 2
561 Manual close signal detected
(Man.Clos.Detect)
Power System
Data 2
OUT ON * LED BO 150 211 1
562 CB CLOSE command for manual closing
(Man.Close Cmd)
Power System
Data 2
OUT * * LED BO 150 212 1
563 CB alarm suppressed (CB Alarm Supp) Power System
Data 2
OUT * * * LED BO
888 Pulsed Energy Wp (active) (Wp(puls)) Energy PMV BI 133 55 205
889 Pulsed Energy Wq (reactive) (Wq(puls)) Energy PMV BI 133 56 205
924 Wp Forward (Wp+=) Energy MVMV 133 51 205
925 Wq Forward (Wq+=) Energy MVMV 133 52 205
928 Wp Reverse (Wp-=) Energy MVMV 133 53 205
929 Wq Reverse (Wq-=) Energy MVMV 133 54 205
1000 Number of breaker TRIP commands (#
TRIPs=)
Statistics OUT
1001 Number of breaker TRIP commands L1
(TripNo L1=)
Statistics OUT
1002 Number of breaker TRIP commands L2
(TripNo L2=)
Statistics OUT
1003 Number of breaker TRIP commands L3
(TripNo L3=)
Statistics OUT
1027 Accumulation of interrupted current L1 (Σ
IL1 =)
Statistics OUT
1028 Accumulation of interrupted current L2 (Σ
IL2 =)
Statistics OUT
1029 Accumulation of interrupted current L3 (Σ
IL3 =)
Statistics OUT
1030 Last fault current Phase L1 (Last IL1 =) Statistics OUT
1031 Last fault current Phase L2 (Last IL2 =) Statistics OUT
1032 Last fault current Phase L3 (Last IL3 =) Statistics OUT
1114 Flt Locator: primary RESISTANCE (Rpri =) Fault Locator OUT ON
OFF
151 14 4
F.No. Description Function Type of
Informa-
tion
Log-Buffers Configurable in Matrix IEC 60870-5-103
Event Log On/Off
Trip (Fault) Log On/Off
Ground Fault Log On/Off
Marked in Oscill. Record
LED
Binary Input
Function Key
Binary Output
Chatter Blocking
Type
Information-No
Data Unit (ASDU)
General Interrogation