Appendix
B-37
7SA6 Manual
C53000-G1176-C156-2
2871 AR: TRIP command 3pole (AR TRIP
3pole)
Automatic Reclo-
sure
OUT * ON LED BO 40 171 2 GI
2889 AR 1st cycle zone extension release (AR
1.CycZoneRel)
Automatic Reclo-
sure
OUT * * LED BO 40 160 1
2890 AR 2nd cycle zone extension release (AR
2.CycZoneRel)
Automatic Reclo-
sure
OUT * * LED BO 40 169 1
2891 AR 3rd cycle zone extension release (AR
3.CycZoneRel)
Automatic Reclo-
sure
OUT * * LED BO 40 170 1
2892 AR 4th cycle zone extension release (AR
4.CycZoneRel)
Automatic Reclo-
sure
OUT * * LED BO 40 172 1
2893 AR zone extension (general) (AR Zone
Release)
Automatic Reclo-
sure
OUT * * LED BO 40 173 1 GI
2894 AR Remote close signal send (AR Remote
Close)
Automatic Reclo-
sure
OUT * ON LED BO 40 129 1
2895 No. of 1st AR-cycle CLOSE com-
mands,1pole (AR #Close1./1p=)
Statistics OUT
2896 No. of 1st AR-cycle CLOSE com-
mands,3pole (AR #Close1./3p=)
Statistics OUT
2897 No. of higher AR-cycle CLOSE com-
mands,1p (AR #Close2./1p=)
Statistics OUT
2898 No. of higher AR-cycle CLOSE com-
mands,3p (AR #Close2./3p=)
Statistics OUT
2901 >Switch on synchro-check function
(>Sync. on)
Synchronism and
Voltage Check
SP * * LED BI BO
2902 >Switch off synchro-check function
(>Sync. off)
Synchronism and
Voltage Check
SP * * LED BI BO
2903 >BLOCK synchro-check function
(>BLOCK Sync.)
Synchronism and
Voltage Check
SP * * LED BI BO
2905 >Start synchro-check for Manual Close
(>Sync. Start MC)
Synchronism and
Voltage Check
SP on
off
* LED BI BO
2906 >Start synchro-check for AR (>Sync. Start
AR)
Synchronism and
Voltage Check
SP on
off
* LED BI BO
2907 >Sync-Prog. Live bus / live line / Sync
(>Sync. synch)
Synchronism and
Voltage Check
SP * * LED BI BO
2908 >Sync-Prog. Dead bus / live line (> Usyn<
U-line>)
Synchronism and
Voltage Check
SP * * LED BI BO
2909 >Sync-Prog. Live bus / dead line (> Usyn>
U-line<)
Synchronism and
Voltage Check
SP * * LED BI BO
2910 >Sync-Prog. Dead bus / dead line (>
Usyn< U-line<)
Synchronism and
Voltage Check
SP * * LED BI BO
2911 >Sync-Prog. Override ( bypass ) (>Sync.
o/ride)
Synchronism and
Voltage Check
SP * * LED BI BO
2930 Synchro-check ON/OFF via BI (Sync. on/
off BI)
Synchronism and
Voltage Check
IntSP ON
OFF
* LED BO
2931 Synchro-check is switched OFF (Sync.
OFF)
Synchronism and
Voltage Check
OUT ON
OFF
* LED BO 41 31 1 GI
2932 Synchro-check is BLOCKED (Sync.
BLOCK)
Synchronism and
Voltage Check
OUT ON
OFF
ON
OFF
LED BO 41 32 1 GI
F.No. Description Function Type of
Informa-
tion
Log-Buffers Configurable in Matrix IEC 60870-5-103
Event Log On/Off
Trip (Fault) Log On/Off
Ground Fault Log On/Off
Marked in Oscill. Record
LED
Binary Input
Function Key
Binary Output
Chatter Blocking
Type
Information-No
Data Unit (ASDU)
General Interrogation