EasyManua.ls Logo

Siemens siprotec 7SA6 - Page 836

Siemens siprotec 7SA6
876 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Appendix
B-36
7SA6 Manual
C53000-G1176-C156-2
2801 AR in progress (AR in progress) Automatic Reclo-
sure
OUT * ON LED BO 40 101 2 GI
2809 AR: Start-signal monitoring time expired
(AR T-Start Exp)
Automatic Reclo-
sure
OUT * ON LED BO 40 174 1
2810 AR: Maximum dead time expired (AR
TdeadMax Exp)
Automatic Reclo-
sure
OUT * ON LED BO 40 175 1
2818 AR: Evolving fault recognition (AR evolv-
ing Flt)
Automatic Reclo-
sure
OUT * ON LED BO 40 118 2 GI
2820 AR is set to operate after 1p trip only (AR
Program1pole)
Automatic Reclo-
sure
OUT * * LED BO 40 143 1
2821 AR dead time after evolving fault (AR Td.
evol.Flt)
Automatic Reclo-
sure
OUT * ON LED BO 40 197 2
2839 AR dead time after 1pole trip running (AR
Tdead 1pTrip)
Automatic Reclo-
sure
OUT * ON LED BO 40 148 2 GI
2840 AR dead time after 3pole trip running (AR
Tdead 3pTrip)
Automatic Reclo-
sure
OUT * ON LED BO 40 149 2 GI
2841 AR dead time after 1phase fault running
(AR Tdead 1pFlt)
Automatic Reclo-
sure
OUT * ON LED BO 40 150 2 GI
2842 AR dead time after 2phase fault running
(AR Tdead 2pFlt)
Automatic Reclo-
sure
OUT * ON LED BO 40 151 2 GI
2843 AR dead time after 3phase fault running
(AR Tdead 3pFlt)
Automatic Reclo-
sure
OUT * ON LED BO 40 154 2 GI
2844 AR 1st cycle running (AR 1stCyc. run.) Automatic Reclo-
sure
OUT * ON LED BO 40 155 2 GI
2845 AR 2nd cycle running (AR 2ndCyc. run.) Automatic Reclo-
sure
OUT * ON LED BO 40 157 2 GI
2846 AR 3rd cycle running (AR 3rdCyc. run.) Automatic Reclo-
sure
OUT * ON LED BO 40 158 2 GI
2847 AR 4th or higher cycle running (AR
4thCyc. run.)
Automatic Reclo-
sure
OUT * ON LED BO 40 159 2 GI
2848 AR cycle is running in ADT mode (AR ADT
run.)
Automatic Reclo-
sure
OUT * ON LED BO 40 130 2 GI
2851 AR: Close command (AR CLOSE Cmd.) Automatic Reclo-
sure
OUT * ON M LED BO 128 128 1
2852 AR: Close command after 1pole, 1st cycle
(AR Close1.Cyc1p)
Automatic Reclo-
sure
OUT * * LED BO 40 152 1
2853 AR: Close command after 3pole, 1st cycle
(AR Close1.Cyc3p)
Automatic Reclo-
sure
OUT * * LED BO 40 153 1
2854 AR: Close command 2nd cycle (and
higher) (AR Close 2.Cyc)
Automatic Reclo-
sure
OUT * * LED BO 128 129 1
2861 AR: Reclaim time is running (AR T-Recl.
run.)
Automatic Reclo-
sure
OUT * * LED BO 40 161 1
2862 AR successful (AR successful) Automatic Reclo-
sure
OUT * * LED BO 40 162 1
2864 AR: 1pole trip permitted by internal AR
(AR 1p Trip Perm)
Automatic Reclo-
sure
OUT * * LED BO 40 164 1 GI
2865 AR: Synchro-check request (AR
Sync.Request)
Automatic Reclo-
sure
OUT * * LED BO 40 165 2 GI
F.No. Description Function Type of
Informa-
tion
Log-Buffers Configurable in Matrix IEC 60870-5-103
Event Log On/Off
Trip (Fault) Log On/Off
Ground Fault Log On/Off
Marked in Oscill. Record
LED
Binary Input
Function Key
Binary Output
Chatter Blocking
Type
Information-No
Data Unit (ASDU)
General Interrogation

Table of Contents