Appendix
B-35
7SA6 Manual
C53000-G1176-C156-2
2731 >AR: Sync. release from ext. sync.-check
(>Sync.release)
Automatic Reclo-
sure
SP * * LED BI BO 40 31 2 GI
2737 >AR: Block 1pole AR-cycle (>BLOCK
1pole AR)
Automatic Reclo-
sure
SP ON
OFF
* LED BI BO 40 32 1 GI
2738 >AR: Block 3pole AR-cycle (>BLOCK
3pole AR)
Automatic Reclo-
sure
SP ON
OFF
* LED BI BO 40 33 1 GI
2739 >AR: Block 1phase-fault AR-cycle (>BLK
1phase AR)
Automatic Reclo-
sure
SP ON
OFF
* LED BI BO 40 34 1 GI
2740 >AR: Block 2phase-fault AR-cycle (>BLK
2phase AR)
Automatic Reclo-
sure
SP ON
OFF
* LED BI BO 40 35 1 GI
2741 >AR: Block 3phase-fault AR-cycle (>BLK
3phase AR)
Automatic Reclo-
sure
SP ON
OFF
* LED BI BO 40 36 1 GI
2742 >AR: Block 1st AR-cycle (>BLK 1.AR-
cycle)
Automatic Reclo-
sure
SP ON
OFF
* LED BI BO 40 37 1 GI
2743 >AR: Block 2nd AR-cycle (>BLK 2.AR-
cycle)
Automatic Reclo-
sure
SP ON
OFF
* LED BI BO 40 38 1 GI
2744 >AR: Block 3rd AR-cycle (>BLK 3.AR-
cycle)
Automatic Reclo-
sure
SP ON
OFF
* LED BI BO 40 39 1 GI
2745 >AR: Block 4th and higher AR-cycles
(>BLK 4.-n. AR)
Automatic Reclo-
sure
SP ON
OFF
* LED BI BO 40 40 1 GI
2746 >AR: External Trip for AR start (>Trip for
AR)
Automatic Reclo-
sure
SP * ON LED BI BO 40 41 2 GI
2747 >AR: External pickup L1 for AR start
(>PickupL1AR)
Automatic Reclo-
sure
SP * ON LED BI BO 40 42 2 GI
2748 >AR: External pickup L2 for AR start
(>PickupL2AR)
Automatic Reclo-
sure
SP * ON LED BI BO 40 43 2 GI
2749 >AR: External pickup L3 for AR start
(>PickupL3AR)
Automatic Reclo-
sure
SP * ON LED BI BO 40 44 2 GI
2750 >AR: External pickup 1phase for AR start
(>Pickup 1ph AR)
Automatic Reclo-
sure
SP * ON LED BI BO 40 45 2 GI
2751 >AR: External pickup 2phase for AR start
(>Pickup 2ph AR)
Automatic Reclo-
sure
SP * ON LED BI BO 40 46 2 GI
2752 >AR: External pickup 3phase for AR start
(>Pickup 3ph AR)
Automatic Reclo-
sure
SP * ON LED BI BO 40 47 2 GI
2781 AR: Auto-reclose is switched off (AR off) Automatic Reclo-
sure
OUT ON
OFF
* LED BO 40 81 1 GI
2782 AR: Auto-reclose is switched on (AR on) Automatic Reclo-
sure
IntSP * * LED BO 128 16 1 GI
2783 AR: Auto-reclose is blocked (AR is
blocked)
Automatic Reclo-
sure
OUT ON
OFF
* LED BO 40 83 1 GI
2784 AR: Auto-reclose is not ready (AR not
ready)
Automatic Reclo-
sure
OUT * ON LED BO 128 130 1 GI
2787 AR: Circuit breaker not ready (CB not
ready)
Automatic Reclo-
sure
OUT * * LED BO 40 87 1
2788 AR: CB ready monitoring window expired
(AR T-CBreadyExp)
Automatic Reclo-
sure
OUT * ON LED BO 40 88 2
2796 AR: Auto-reclose ON/OFF via BI (AR on/
off BI)
Automatic Reclo-
sure
IntSP * * LED BO
F.No. Description Function Type of
Informa-
tion
Log-Buffers Configurable in Matrix IEC 60870-5-103
Event Log On/Off
Trip (Fault) Log On/Off
Ground Fault Log On/Off
Marked in Oscill. Record
LED
Binary Input
Function Key
Binary Output
Chatter Blocking
Type
Information-No
Data Unit (ASDU)
General Interrogation

Table of Contents