Introduction
1.3 Characteristics
SIPROTEC, 7SJ61, Manual
C53000-G1140-C210-1, Release date 02.2008
24
Ground Fault Protection 50N, 51N
Three definite time overcurrent protective elements and one inverse time overcurrent protective element for
high-resistance ground faults in grounded systems;
Different curves of common standards are available for 51 and 51N, or a user-defined characteristic;
In-rush restraint with second harmonic oscillation;
Instantaneous tripping by any overcurrent element upon switch onto fault is possible.
Dynamic Cold Load Pick-up Function 50C, 50NC, 51C, 51NC, 67C, 67NC
Dynamic changeover of time overcurrent protection settings, e.g. when cold load conditions are anticipated;
Detection of cold load condition via circuit breaker position or current threshold;
Activation via automatic reclosure (AR) possible;
Start also possible via binary input.
Single-Phase Overcurrent Protection
Evaluation of the measured current via the sensitive or insensitive ground current transformer;
Suitable as differential protection that includes the neutral point current on a transformer side, a generator
side or a motor side or for a grounded reactor set;
As tank leakage protection against illegal leakage currents between transformer casing and ground.
Negative Sequence Protection 46
Evaluation of negative sequence component of the currents;
Two definite-time elements 46-1 and 46-2 and one inverse-time element 46-TOC; curves of common stan-
dards are available for 46-TOC.
Motor Starting Protection 48
Inverse time tripping characteristic based on an evaluation of the motor starting current;
Definite time delay for blocked rotor.
Motor Restart Inhibit 66, 86
Approximate replica of excessive rotor temperature;
Startup is permitted only if the rotor has sufficient thermal reserves for a complete startup;
Disabling of the start inhibit is possible if an emergency startup is required.
Load Jam Protection for Motors 51M
Protection of motors during sudden rotor blocking
Evaluation of the positive sequence system of phase currents
Evaluation of the circuit breaker switching state
Blocking of function during motor standstill and during motor startup