Introduction
1.3 Characteristics
SIPROTEC, 7SJ61, Manual
C53000-G1140-C210-1, Release date 02.2008
25
Thermal Overload Protection 49
Thermal profile of energy losses (overload protection has total memory capability);
True r.m.s. calculation;
Adjustable thermal alarm level;
Adjustable alarm level based on current magnitude;
Additional time constant setting for motors to accommodate the motor at standstill;
Integration of ambient temperature or coolant temperature is possible via external temperature sensors and
RTD-Box.
Monitoring Functions
Availability of the device is greatly increased because of self-monitoring of the internal measurement circuits,
power supply, hardware, and software;
Supervision of the current transformer secondary circuits by means of sum and symmetry checks.
Trip circuit monitoring;
Phase rotation check.
Ground Fault Detection 50N(s), 51N(s)
Two-element ground fault detection: High-current element 50Ns-1 and 50Ns-2;
High sensitivity (as low as 1 mA);
The overcurrent protection element may be operated with either a definite time or an inverse time delay;
One user-defined and two logarithmic-inverse current/time curves are available for inverse time O/C protec-
tion;
Optionally applicable as additional ground fault protection.
Intermittent Ground Fault Protection
Detects and accumulates intermittent ground faults;
Tripping after configurable total time.
Automatic Reclosing System 79
Single-shot or multi-shot;
With separate dead times for the first and all succeeding shots;
Protective elements that initiate automatic reclosing are selectable. The choices can be different for phase
faults and ground faults;
Different programs for phase and ground faults;
Interaction to time overcurrent protection element and ground fault elements. They can be blocked in de-
pendence of the reclosing cycle or released instantaneously;
Breaker Failure Protection 50 BF
Checking current flow and/or evaluation of the circuit breaker auxiliary contacts;
Initiated by the tripping of any integrated protective element that trips the circuit breaker;
Initiation possible via a binary input from an external protective device.