EasyManuals Logo

Siemens SIPROTEC 7SJ61 User Manual

Siemens SIPROTEC 7SJ61
454 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #25 background imageLoading...
Page #25 background image
Introduction
1.3 Characteristics
SIPROTEC, 7SJ61, Manual
C53000-G1140-C210-1, Release date 02.2008
25
Thermal Overload Protection 49
• Thermal profile of energy losses (overload protection has total memory capability);
• True r.m.s. calculation;
• Adjustable thermal alarm level;
• Adjustable alarm level based on current magnitude;
• Additional time constant setting for motors to accommodate the motor at standstill;
• Integration of ambient temperature or coolant temperature is possible via external temperature sensors and
RTD-Box.
Monitoring Functions
• Availability of the device is greatly increased because of self-monitoring of the internal measurement circuits,
power supply, hardware, and software;
• Supervision of the current transformer secondary circuits by means of sum and symmetry checks.
• Trip circuit monitoring;
• Phase rotation check.
Ground Fault Detection 50N(s), 51N(s)
• Two-element ground fault detection: High-current element 50Ns-1 and 50Ns-2;
• High sensitivity (as low as 1 mA);
• The overcurrent protection element may be operated with either a definite time or an inverse time delay;
• One user-defined and two logarithmic-inverse current/time curves are available for inverse time O/C protec-
tion;
• Optionally applicable as additional ground fault protection.
Intermittent Ground Fault Protection
• Detects and accumulates intermittent ground faults;
• Tripping after configurable total time.
Automatic Reclosing System 79
• Single-shot or multi-shot;
• With separate dead times for the first and all succeeding shots;
• Protective elements that initiate automatic reclosing are selectable. The choices can be different for phase
faults and ground faults;
• Different programs for phase and ground faults;
• Interaction to time overcurrent protection element and ground fault elements. They can be blocked in de-
pendence of the reclosing cycle or released instantaneously;
Breaker Failure Protection 50 BF
• Checking current flow and/or evaluation of the circuit breaker auxiliary contacts;
• Initiated by the tripping of any integrated protective element that trips the circuit breaker;
• Initiation possible via a binary input from an external protective device.

Table of Contents

Other manuals for Siemens SIPROTEC 7SJ61

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIPROTEC 7SJ61 and is the answer not in the manual?

Siemens SIPROTEC 7SJ61 Specifications

General IconGeneral
BrandSiemens
ModelSIPROTEC 7SJ61
CategoryController
LanguageEnglish

Related product manuals