EasyManua.ls Logo

Siemens SIPROTEC 7SS523 V3.2

Siemens SIPROTEC 7SS523 V3.2
430 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Functions
108
7SS52 V4 Manual
C53000-G1176-C182-1
K
b
= I
scc max
/ I
sat
The saturation current I
sat
can be calculated from the rated current I
pn
and the ef-
fective factor of the symmetrical rated short-circuit current K'
ssc
(which used to be
called operational overcurrent factor n')
I
sat
= I
pn
* K'
ssc
I
pn
= primary rated current
The factor K'
ssc
can be calculated from the data and the actual burden of the current
transformers:
K'
ssc
= (R
ct
+R
b
) / (R
ct
+R'
b
) * K
ssc
with R'
b
= R
l
+ R
relay
R
ct
= secondary winding resistance (75 °C)
R
b
= resistive rated burden
R'
b
= connected burden
R
l
= line resistance
R
relay
= protection burden
K'
ssc
= factor of the symmetrical rated short-circuit current
For burden factors K
b
< 2, a k-factor of 0.6 is sufficient. For K
b
> 2, the minimum
k-factor is:
with K
b
> 2
The setting value k thus obtained comprises 20 % safety.
The basis for this fomula is summarized in the Chapter A.2, page 333.
The CT with the highest burden factor K
b
must be the basis for selecting the
factor k.
Id> BZ The parameter Id> BZ (6102/CU) is used to set the threshold for the bus zone-se-
lective protection in the presence of small fault current.
For pickup and tripping of the protection, only those normalized currents I
d
are consid-
ered which exceed the diff-current threshold set in the parameter Id> BZ (6102/CU).
A current below this threshold causes the pickup to drop off.
To calculate the highest permissible setting, determine first the smallest fault current
to be expected in case of a busbar short-circuit. The set value should have an extra
response margin of about 20%. The lowest permitted setting is I
max load
+ 30%.
1.3 I
max load
< Id> BZ < 0.8 I
scc min
k
K
b
4Kb 1
-----------------------
>

Table of Contents

Related product manuals