EasyManua.ls Logo

Siemens SIPROTEC 7SS523 V3.2

Siemens SIPROTEC 7SS523 V3.2
430 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
End Fault Protection
135
7SS52 V4 Manual
C53000-G1176-C182-1
Tabelle 5-1 Allocation of bus coupler currents to measuring systems
Figure 5-31 Short-circuit in the dead zone of the bus coupler with the circuit breaker closed
5.4.2.2 Circuit Breaker Open
If a short-circuit occurs in the dead zone with open circuit breaker and closed isolators,
the wrong bus zone (BZA) would be tripped without appropriate countermeasures
(Figure 5-32, page 135). The reason for the incorrect tripping is as follows:
I
BZA
= I (feed)
BZA
+ I
CP
→ ∆I
SBZA
= I
CP
> 0 ("Fault in BZA")
I
BZB
= I (feed)
BZB
+ I
CP
→ ∆I
BZB
= 0 ("No fault in BZB")
Therefore the status of the bus coupler circuit breaker must be considered to prevent
erroneous tripping ">CB OFF" (FNo. 7617/BU) .
With the circuit breaker open, the coupler current for measuring system BZA and for
measuring system BZB is set to zero. As a result, the fault current I
CP
is only detected
and tripped in measuring system BZB. The resulting allocation of the coupler currents
with the circuit breaker open can be seen in Tabelle 5-1, page 135 "after T-BF" (Figure
5-32, page 135).
Figure 5-32 Short-circuit in the dead zone with the circuit breaker open
If the bus coupler comprises two current transformers ("2-bay coupler"), both coupler
currents are set to zero with the CB open (Figure 5-33, page 136).
Meas. system Reaction
BZ A BZ B
Current allocation until
expiry of T-BF
I
CP
, I
1
I
CP
, I
2
BZ A trip
BZ B stable
Current allocation after
delay time T-BF or after
detection of ”CB TRIP”
I
CP
= 0
I
1
=0
(I
CP
= 0)
I
2
BZ A healthy
BZ A trip by
special treatment

Table of Contents

Related product manuals