EasyManua.ls Logo

Siemens SIPROTEC 7SS523 V3.2

Siemens SIPROTEC 7SS523 V3.2
430 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Installation and Commissioning
266
7SS52 V4 Manual
C53000-G1176-C182-1
The operator addresses for the control of the other relays are stored on the subse-
quent addresses. In the case of an operation via the membrane keyboard, a once
entered password is memorized until the address block is left. In the case of an ope-
ration via DIGSI, the password has to be entered again for each control action (relay
on or off).
7.3.4 Testing the System Port
Preliminary re-
marks
If the device has a system port and uses this for communicating with a control center,
you can test with the DIGSI device operation whether indications are correctly trans-
mitted. You must avoid to use this test possibility during live operation.
The port test is made in the DIGSI mode Online:
Double-click the directory Online. The operating functions for this device will ap-
pear.
Click Test. In the right pane of the picture the available functions appear.
Double-click in the list Generate Indications. The dialog box Generate Indica-
tions is opened (see Figure 7-10, page 267).
Input sequence for deactivating trip relay 1
4802 TRIP RELAY1
- DEACTIVATE?
E key ->
ENTER PASSWORD:
Entry of the password
Password
F3,F1,F3,F1,F3,F1 ->
4802 TRIP RELAY1
- DEACTIVATE?
E key ->
4802 TRIP RELAY1
SUCCESSFUL
In the event of a negative
feedback: „not successful“
Danger!
The sending or receiving of annunciations via the system port by means of the test
function is a real information exchange between SIPROTEC and the control center.
This information would execute the corresponding functions (e.g. follow-up com-
mands) in the control center.

Table of Contents

Related product manuals