Parameter assignment
6.3 Suggested settings
SIRIUS 3RW52 Soft Starter
Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005
101
6.3 Suggested settings
Application
Starting voltage [%]
Ramp up time [s]
Current limiting
Stopping time [s]
Conveyor belt (full)
70
5
7 × I
e
10
Roller conveyor (full)
60
5
7 × I
e
10
Compressor (without pressure)
50
4
4 × I
e
Not relevant
Small ventilator (fan) 40 2 4 × I
e
Not relevant
Pump
1)
40
3
4 × I
e
10
Hydraulic pump
40
2
4 × I
e
Not relevant
Agitator
40
2
4 × I
e
Not relevant
Milling machine
40
4
4 × I
e
Not relevant
1)
It is recommended that the "Soft torque" function is activated.