Example circuits
A.1 Main circuit connection
SIRIUS 3RW52 Soft Starter
216 Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005
A.1.2 Feeder assembly, type of coordination 1 with fuses
Feeder assembly
If galvanic isolation is required, install a main or line contactor between the
3RW52 soft starter and the fuses.
Do not connect the main and line contactor between the 3RW52 soft starter and the motor.
The 3RW52 soft starter could otherwise indicate a "Missing load" fault in case of a start
command and delayed connection of the contactor.