Mounting and dismantling
4.4 Installing, mounting and removing the 3RW5 HMI
SIRIUS 3RW52 Soft Starter
Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005
67
4.4.6 Installing the High Feature 3RW5 HMI in the control cabinet door
Requirements
Ⴠ Note the mounting positions, minimum clearances and ambient conditions stated on the
data sheet.
Ⴠ 3RW5 HMI High Feature (accessory)
Ⴠ HMI connecting cable (accessory) of suitable length connected to the 3RW52 soft starter
Ⴠ Cutout of suitable size in the control cabinet door
Ⴠ Device depth of the High Feature 3RW5 HMI:
– Total depth: 32 mm
– Embedded depth: 26 mm
Ⴠ Permissible wall thickness of the control cabinet door:
– Without IP65 door mounting kit: 1.5 to 3.0 mm
– With IP65 door mounting kit: 1.0 to 7.0 mm
For using door mounting kit IP65:
Ⴠ IP65 door mounting kit (accessory)
The fixing brackets with marking "002" are intended for a 3RW5 HMI High Feature.
Ⴠ Screwdriver PZ2
Procedure without door mounting kit IP65
Place the 3RW5 HMI High Feature in the cutout of the control cabinet door . Ensure that
the 3RW5 HMI High Feature engages audibly in the 4 fixtures
ཱ.