EasyManua.ls Logo

Siemens SIRIUS 3RW52 - Installing the Standard 3 RW5 HMI on a Flat Surface

Siemens SIRIUS 3RW52
258 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Mounting and dismantling
4.4 Installing, mounting and removing the 3RW5 HMI
SIRIUS 3RW52 Soft Starter
Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005
71
4.4.7 Installing the Standard 3RW5 HMI on a flat surface
Requirements
Note the mounting positions, minimum clearances and ambient conditions stated on the
data sheet.
3RW5 HMI Standard (accessory)
Level surface, e.g. sufficiently strong mounting plate
2 properly executed drill holes with thread or plugs on the level surface. Refer to the
drilling pattern (Page 210).
2 head screws M4 x 12 DIN ISO 7045 to fit the drill-holes
Screwdriver (depending on the drive of the screws)
2 push-in lugs (accessory) for wall mounting
HMI connecting cable (accessory) of suitable length connected to the 3RW52 soft starter
Procedure
Observe the coding of the plug and socket .
Lock the connector in the socket
.
The HMI connecting cable in the cable duct of the 3RW5 HMI Standard may only be
routed downward.
Make sure that you install the cable in accordance with EMC requirements. For example,
install data cables separately from the motor cable. Connect both sides of shielded
cables over a large surface area.

Table of Contents

Other manuals for Siemens SIRIUS 3RW52

Related product manuals