Parameter assignment
6.8 Parameterize the response to bus errors and output 13, 14 (ON / RUN)
SIRIUS 3RW52 Soft Starter
108 Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005
6.8 Parameterize the response to bus errors and output 13, 14
(ON / RUN)
Requirements
3RW52 soft starter from firmware version V2.0.1
During the activation you must be able to switch off the supply voltage
(control supply voltage).
Procedure
1. Press the MODE key during operation for longer than 2 seconds until the
STATE / OVERLOAD LED flickers green and press and hold the MODE key.
2. Switch off the power supply (control supply voltage) of the 3RW52 soft starter for at least
5 seconds. After the 5 seconds have elapsed, you can release the MODE key.
3. Press and hold the MODE and TEST / RESET keys.
4. Switch on the power supply (control supply voltage) of the 3RW52 soft starter again.
When the SOFT TORQUE and RESET MODE LEDs flicker green, the parameterization
mode is active. You can release the MODE and TEST / RESET keys.
5. Select the desired parameter using the MODE key.
You can recognize your selection by the color of the STATE / OVERLOAD LED.
LED
STATE / OVERLOAD
Parameters to be changed
Off
No selection
Lights up green
Control via digital input
Lights up red
Output ON / RUN