Messages and diagnostics
9.7 Execute HMI diagnostics with the 3RW5 HMI High Feature
SIRIUS 3RW52 Soft Starter
Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005
185
9.7 Execute HMI diagnostics with the 3RW5 HMI High Feature
With the diagnosis, you can display the diagnosis state of the 3RW5 HMI High Feature and
check correct functioning of the 3RW5 HMI High Feature with various tests.
Requirements
Ⴠ 3RW5 HMI High Feature (accessory)
Menu: "Diagnosis > HMI"
Note
Self-tests
To be able to start the self
-tests with a 3RW5 HMI High Feature with firmware version V3.1,
ected to the 3RW5 soft starter must be switched off.
3RW5 HMI High Feature with firmware version
V3.1 or earlier: During the self-test, you
tch off the motor on the 3RW5 HMI High Feature. If you are controlling the motor
HMI High Feature, switch off the motor before a self-test.
Diagnosis state Shows all active diagnostic messages
(faults, warnings, device state).
Self-test Test LEDs The device LEDs of the 3RW5 HMI High Feature are tested
one after the other. The display shows which device LED is
currently being controlled. Navigate through the test operation
Test buttons The 3RW5 HMI High Feature keys are tested one after the
other. The display shows which keys must be actuated in
sequence in order to perform the test.
Test display The 3RW5 HMI High Feature runs a color program on the
display. Navigate through the test operation with the OK key.