Parameter assignment
6.11 Parameterize analog output AQ via the 3RW5 HMI High Feature
SIRIUS 3RW52 Soft Starter
Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005
123
Result
You have adjusted the output signal of the analog output.
PLC at analog output
You can connect the analog output of the 3RW52 soft starter to a free analog output of the
PLC. Make sure that the analog input of the PLC is not connected to the supply voltage
(control supply voltage) of the 3RW52 soft starter and is floating.
You will find further information in the application example in the FAQs
(https://support.industry.siemens.com/cs/ww/en/view/109778700
).