Parameter assignment
6.12 Parameterizing the High Feature 3RW5 HMI
SIRIUS 3RW52 Soft Starter
Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005
125
Do control after log off This parameter describes the response after logging off while the motor is running.
x Continue with motor control
The master control is retained by the 3RW5 HMI High Feature.
x Stop motor and give back control (factory setting)
The motor stops and the master control is no longer with the 3RW5 HMI High Feature.
Messages to show If errors and/or warnings are enabled, they will appear as pop-up windows in the display of
the 3RW5 HMI High Feature as soon as they occur.
x Errors
– Enable (factory setting)
– Disable
x Warnings
– Enable (factory setting)
– Disable
Operation display You can select up to 5 different measured values from a list of measured values. These
measured values are then shown in the operation display of the 3RW5 HMI High Feature.
You will find further information on measured values in chapter Monitoring the measured
values of the 3RW52 soft starter with the 3RW5 HMI High Feature (Page 154).
x Measured value 1: Phase current average (%) (factory setting)
x Measured value 2: Phase current average (rms) (factory setting)
x Measured value 3: Phase current I L1 (rms) (factory setting)
x Measured value 4: Phase current I L2 (rms) (factory setting)
x Measured value 5: Phase current I L3 (rms) (factory setting)
Languages The required language is set in the "Languages" menu.
x English (factory setting)
x German
x French
x Spanish
x Italian
x Portuguese
x Chinese
x Additional language
1)
(Page 168)