Messages and diagnostics
9.9 Self-test (user-test)
SIRIUS 3RW52 Soft Starter
190 Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005
Position of the rotary coding
switch "Rated operational
current I
e
of the motor"
Lights up red
Off
Off
Off
Off
Current detection test
"STATE / OVERLOAD"
Flickers red
Off
In case of error: System LEDs
(RN, ER, MT) flashing.
Device error, replace device.
Motor overload protection test
"STATE / OVERLOAD" LED
Flashes red
Off
In case of error: System LEDs
(RN, ER, MT) flashing.
Device error, replace device.
"ER" LED
Flashes red
In case of error: System LEDs
(RN, ER, MT) flashing.
Device error, replace device.
Self-test of the 3RW5 HMI High Feature
You will find more information on the self-test of the 3RW5 HMI High Feature in Chapter
Execute HMI diagnostics with the 3RW5 HMI High Feature (Page 185).