3.6 Operating modes and master control function
SIRIUS 3RW52 Soft Starter
36 Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005
Operating mode "Manual - bus"
Fetching control
SIRIUS Soft Starter ES (TIA Portal) Premium / Professional actively fetches control from
"Automatic" mode in response to a command to this effect.
Brief overview: Window "Task Card" > Tab "Online Tools" > "SIRIUS Control Panel >
Master Control > Get Control"
Giving back control
SIRIUS Soft Starter ES (TIA Portal) Premium / Professional actively passes control to
"Automatic" mode in response to a command to this effect.
Brief overview: Window "Task Card" > Tab "Online Tools" > "SIRIUS Control Panel >
Master Control > Release Control"
Withdrawal of master control by other control sources
Master control is withdrawn from the operating mode "manual - bus" by the operating mode
"manual - local" as follows:
Activation of the "Manual operation local - input controlled" bit in the process image
output (PIQ) or in the data table "Process image output (PIQ)"
(depending on the 3RW5 communication module).
"LOCAL / REMOTE" action on the 3RW5 HMI
Command in SIRIUS Soft Starter ES (TIA Portal)
(local interface on the 3RW5 HMI High Feature)
Brief overview: Window "Task Card" > Tab "Online Tools" > "SIRIUS Control Panel >
Master Control > Get Control"