5 Uninterruptible 24 V power supply
Integration of a SITOP 24V power supply in PCS 7
Entry ID: 10948108, V3.2, 01/2019
43
Siemens AG
2019 All rights reserved
5.2.4 Parameterizing messages
Open the message configurations of the "MonDiL" blocks one after the other and
carry out the following modifications:
1. At "SIG1" of buffer monitoring (1), change the message text and the message
class to "Warning high".
2. At "SIG1" und "SIG2" of battery monitoring (2), change the message text and
the message class to "Alarm high".
3. At "SIG1" of status monitoring (3), change the message text and the message
class to "Process Message With Acknowledgement".
Figure 5-18:
1
2
3
Note
If you need message texts in several languages, you use the menu command

Manager to change the language for display texts and adapt the text in the
message configuration for the set language.