Appendix A
A.1 Modbus, EIP, HART & N2 Profile Mappings
F US Clamp-on Communications Protocol Manual
Hardware Installation Manual, 11/2015, A5E34981613-AC
139
Time: Hour
30104
2
Integer
Analog_In
3
Float
n/a
ADI(Int)
4
1
Time: Minute
30105
2
Integer
Analog_In
4
Float
n/a
ADI(Int)
5
1
Time: Second
30106
2
Integer
Analog_In
5
Float
n/a
ADI(Int)
6
1
C1 Avg Energy
Rate
30201 4 Real Analog_In 6 Float 129 40-28h S ADF(Float) 1 1
C1 Inst.Energy
Rate
30195 4 Real Analog_In 7 Float n/a ADF(Float) 2 1
C1 Energy Rate
Units
30653 8 String String_In 4 UINT16 131 40-28h BD(Byte) 9 8
C1 Energy Total
30207
4
Real
Analog_In
8
Float
129
43-2Bh
ADF(Float)
3
1
C1 EnergyTotal
Units
30661 8 String String_In 8 UINT16 131 43-2Bh BD(Byte) 17 8
C1 Inst.Flow
Rate
30109 4 Real Analog_In 9 Float 129 6-06h ADF(Float) 4 1
C1 Avg Flow
Rate
30121 4 Real Analog_In 10 Float 129 1-01h P ADF(Float) 5 1
C1 Flow Rate
Units
30517 8 String String_In 12 UINT16 131 1-01h BD(Byte) 25 8
C1 Total
30145
4
Real
Analog_In
11
Float
129
34-22h
ADF(Float)
6
1
C1 Total Units
30557
8
String
String_In
16
UINT16
131
34-22h
BD(Byte)
33
8
C1 Supply Temp
30303
4
Real
Analog_In
12
Float
n/a
ADF(Float)
7
1
C1 Supply Temp
Units
30773 8 String String_In 20 UINT16 n/a BD(Byte) 41 8
C1 Return Temp
30309
4
Real
Analog_In
13
Float
n/a
ADF(Float)
8
1
C1 Return Temp
Units
30781 8 String String_In 24 UINT16 n/a BD(Byte) 49 8
C1 Temp
Difference
30315 4 Real Analog_In 14 Float n/a ADF(Float) 9 1
C1 Temp Diff
Units
30789 8 String String_In 28 UINT16 n/a BD(Byte) 57 8
C1 Status
/Alarms: Spacing
10021 1 Bit Coil Binary_In 0 UINT16 n/a DI(Dig In) 1 1
C1 Status
/Alarms: Empty
10022 1 Bit Coil Binary_In 0 UINT16 n/a DI(Dig In) 3 1
C1 Status
/Alarms: Rate
10023 1 Bit Coil Binary_In 0 UINT16 n/a DI(Dig In) 4 1
C1 Status
/Alarms: Fault
10024 1 Bit Coil Binary_In 0 UINT16 n/a DI(Dig In) 5 1
C1 Status
/Alarms: Aeration
10025 1 Bit Coil Binary_In 0 UINT16 n/a DI(Dig In) 6 1
C1 Status
/Alarms: Memory
10026 1 Bit Coil Binary_In 0 UINT16 n/a DI(Dig In) 7 1
C1 Status
/Alarms: Makeup
10027 1 Bit Coil Binary_In 0 UINT16 n/a DI(Dig In) 8 1
C1 Status
/Alarms: Interface
10028 1 Bit Coil Binary_In 0 UINT16 n/a DI(Dig In) 9 1
C1 Status
/Alarms:
Zeromatic
10030 1 Bit Coil Binary_In 0 UINT16 n/a DI(Dig In) 2 1